BEA Stanley Dip Switch I Manual Do Utilizador

Página de 20
SIZE:
DRAWN BY:
TITLE: PARALLINK, STANLEY MP CONTROL,
MAGIC FORCE OPERATOR
A
NOTES: 1) MAGIC FORCE AUX. SWITCH #4 SHOULD OPEN AT APPROX. 65-70 DEGREES. FOR MAGIC SWING REFER TO INHIBIT
SWITCH BEA PT# 10 SSINHL OR 10SSINHR.
2) DOOR CONTROL SW2 SWITCH BANK SET DIPSWITCH # 1 & 3 TO THE OFF (TIMER) POSITION.
3) RH MOTOR SHOWN, REVERSE MOTOR SWITCH ON PARALINK FOR LH MOTOR.
4) BODYGUARD MUST BE PROGRAMMED TO RELAY VALUE 2. DEFAULT IS 1.
5) INSTALL JUMPER AT CONTROL ON TERMINAL 6 & 8 IF NO BREAKOUT SWITCH.
100 ENTERPRISE DRIVE
PITTSBURGH, PA  15275
PHONE: (412) 249-4100
FAX:       (412) 249-4101
EMAIL:   www.beasensors.com
REV BY:
TUC
TUC
80.0203.01
SCALE:
DATE:
NONE
19 SEP 2005
PART NO:
SHEET
1 OF 1
STANLEY MP
CONTROL
BLACK
WHITE
Common
N/O
N/C
RH DOOR
AUX. SWITCH #4
LOCATED ON TOP
OF OPERATOR
Common
N/O
N/C
LH DOOR
AUX. SWITCH #4
LOCATED ON TOP
OF OPERATOR
BODYGUARD (See Note #4)
PUSH TO TEST
24 V 
TRANSFORMER
IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.
FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,
CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOT
LEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THE
DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THE
AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM