D. PIPING DIAGRAM 
 
Figure 16 
– DHW Piping  
 
Figure 17 
– Piping with Recirculation 
E. PRESSURE RELIEF VALVE 
An external pressure relief valve must be installed on this water heater. When 
installing, observe the following guidelines. Failure to comply with these guidelines 
can result in substantial property damage, personal injury, or death. 
 
This water heater must be prov
ided with an approved 150 psi, ¾” ASME HV Valve 
that must be installed on the DHW outlet line (See Figure 18). The 150 psi Pressure 
Relief Valve must be installed on the DHW supply line to ensure a compliant 
installation and safe operation.  
 
This water heater has a high-temperature shut-off switch built in as a standard safety 
feature. Therefore, a “pressure only” relief valve is required. DO NOT operate this 
water heater before the supplied pressure relief valve is installed with sufficient 
relieving capacity in accordance with the ASME rating plate on the water heater.  
 
Pressure relief valves must be installed as close to the water heater as possible. No 
other valves should be placed between the pressure relief valve and the appliance. 
DO NOT install a relief valve with a pressure rating greater than 150 psi. This is the 
maximum allowable relief valve setting for this water heater.  
 
After installing the relief valve and filling and pressurizing the system, test the 
operation of the valve by lifting the lever. Make sure the valve discharges freely. If 
the valve fails to operate correctly, replace it with a new relief valve. Ensure that the 
Figure 18 
– Relief Valve Details