11
BOILER DISPLAy
IV- HOW TO SET PARAMETERS
Press and hold the “SteP” button.
1.
While holding the “SteP” button down, press and hold
2.
the “mOde” button.
Hold both buttons down together for several seconds
Hold both buttons down together for several seconds
3.
until [COde] appears on the display.
Release “SteP” and “mOde” buttons. [Code] will stay
Release “SteP” and “mOde” buttons. [Code] will stay
4.
lit on on the display.
NOTE:
if [COde] is not displayed after several seconds,
release “SteP” and “mOde” buttons and press “mOde” several
times to return display to [StBy]. then repeat step 2 again.
Press the “SteP” button once. display will show “C”
5.
and a random number.
adjust the number displayed to [C-05] by using the “+”
adjust the number displayed to [C-05] by using the “+”
6.
and “-” buttons.
Press the “StORe” button.
Press the “StORe” button.
7.
IMPORTANT: The boiler control will automati-
cally exit [CODE] mode after 10 minutes of no
activity.
Press the “mOde” button several times until [PaRa] is
8.
displayed.
using the six buttons on the front of the boiler (below)
and the proper code, the boiler can be both monitored and modified
using the digital display.
Perform the following steps with the boiler powered on and in standby
[STBy] mode:
Press the “SteP” button several times until [P-XX] is
9.
displayed. the XX represents the parameter that will be
changed. the parameter’s value will then be displayed.
changed. the parameter’s value will then be displayed.
note: for parameter 1-4 display will read “1.”, then the param-
eter setting.
use the “+” or “-” buttons to set the desired value.
10.
Press the “StORe” button. Steps 9-11 can now be
11.
repeated for additional parameter changes or continue
to step 12 to exit.
to step 12 to exit.
IMPORTANT: Store MUST be pressed after
EVERy parameter change. The change is ac-
cepted if the display blinks twice.
Press the “ReSet” button to exit.
12.
IMPORTANT: After making changes to pa-
rameters, record the changes made on the last
page of this manual and leave a copy with the
boiler for future reference.