Utica Boilers UB95M-200 Verweisanleitung

Seite von 20
11
BOILER DISPLAy
IV- HOW TO SET PARAMETERS
Press and hold the “SteP” button.
1. 
While holding the “SteP” button down, press and hold 
2. 
the “mOde” button.
Hold both buttons down together for several seconds 
3. 
until [COde] appears on the display.
Release “SteP” and “mOde” buttons. [Code] will stay 
4. 
lit on on the display.
NOTE:
 if [COde] is not displayed after several seconds, 
release “SteP” and “mOde” buttons and press “mOde” several 
times to return display to [StBy].  then repeat step 2 again.
Press the “SteP” button once. display will show “C” 
5. 
and a random number.
adjust the number displayed to [C-05] by using the “+” 
6. 
and “-” buttons.
Press the “StORe” button.
7. 
IMPORTANT: The boiler control will automati-
cally exit [CODE] mode after 10 minutes of no 
activity.
Press the “mOde” button several times until [PaRa] is 
8. 
displayed.
using the six buttons on the front of the boiler (below)
 and the proper code, the boiler can be both monitored and modified 
using the digital display.
Perform the following steps with the boiler powered on  and in standby 
[STBy] mode:
Press the “SteP” button several times until [P-XX] is 
9. 
displayed. the XX represents the parameter that will be 
changed. the parameter’s value will then be displayed. 
note: for parameter 1-4 display will read “1.”, then the param-
eter setting.
use the “+” or “-” buttons to set the desired value.
10. 
Press the “StORe” button. Steps 9-11 can now be 
11. 
repeated for additional parameter changes or continue 
to step 12 to exit.
IMPORTANT:  Store  MUST  be  pressed  after 
EVERy  parameter  change.  The  change  is  ac-
cepted if the display blinks twice.
Press the “ReSet” button to exit.
12. 
IMPORTANT:  After  making  changes  to  pa-
rameters, record the changes made on the last 
page of this manual and leave a copy with the 
boiler for future reference.