  5.  Check the vent system seams and joints and ensure that there is no  
      discharge of flue products into the room.
  6.  Check the input rate.
For  appliance  installation  locations  with  elevations  above  6500  feet  
(1982  meters)  refer  to  HIGH ALTITUDE  INSTALLATIONS  section  of  this 
manual.
    a.  Attach a pressure gauge (manometer) to the manifold pressure tap  
        (Figure 16) and refer to Table 4, page 20 for correct pressure.
    b.  Use this formula to “clock” the meter. Be sure other gas consuming  
        appliances are not operating during this interval.
        3600  
X  H  =  Btuh
             T
Should it be necessary to adjust the gas pressure to the burner, to obtain  
the full input rate, the steps below should be followed:
 
T =  Time in seconds to burn 1 cubic foot of gas. (With a stopwatch read 
the gas meter and measure the amount of time required for the 
heater to consume 1 cubic foot of gas.)
 
H = Heating value of gas (in Btu’s per cubic foot of gas).
 
Btuh = Actual heater input rate, in Btuh.
  EXAMPLE: (Using (A)JWSH100199N Model)
  T = 25.25 seconds
  H = 1050 Btu/ft.
3
  BTUH = ?
For high altitude installations, compare result to the derated input required 
for the elevation at the installation location.
  c.  Remove the pressure regulator cover screw and adjust the pressure by 
turning the adjusting screw with a small screwdriver. Do not exceed 4.0" 
(1 kPa) natural gas models and 10.0" W.C. (2.5Kpa) on the propane 
models.
   
 Clockwise to increase gas pressure and input rate.
   
Counterclockwise to decrease gas pressure and input rate.
  d.  “Clock” the meter as in step (b) above.
  e.  Repeat steps (c) and (d) until the specified input rate is achieved.
  f.  Turn the manual gas valve to “OFF”. Replace the pressure regulator  
      cover  screw.  Remove  the  pressure  gauge  or  manometer  from  the  
      manifold pressure tap. Replace the set screw in the manifold pressure  
      tap.  If the gas pressure regulator cannot be adjusted to give the full   
      input rating with sufficient gas pressure at the valve, check to ensure  
      the  unit is equipped with the correct orifice.
ADJUSTMENT PROCEDURE
INITIAL START-UP - (A)JWSH100199 & (A)JWSH100250
Main line gas pressure to the water heater for natural gas should be between 
a  maximum  of  10.5"  (2.59Kpa  for  natural  gas)  W.C.  (14.0"/3.45Kpa  for 
propane) and a minimum as shown in Table 4: that is, for Natural Gas 4" 
(.98Kpa) W.C. and 9.0" (1.97Kpa) for Propane Gas. The inlet gas pressure 
must not exceed the maximum value. A service regulator must be installed 
within 10' (305 cm) of the unit.
The (A)JWSH100199 and (A)JWSH100250 models incorporate a new gas 
control, which operates at 0"W.C. (0kPa) for both natural and propane gas. 
These models are configured prior to being shipped from the factory and 
no adjustments are necessary prior to startup. The controller monitors the 
air-flow and makes adjustments to the fan speed which in effect controls 
the amount of gas flow. Therefore, the unit will self-adjust to acquire the 
correct amount of input.
Once  the  unit  is  installed  and  filled  with  water  and  the  inlet  pressures 
confirmed, simply turn the switch "on" and observe operation. Cycle the unit 
"off" and "on" several times to ensure proper operation.
OPERATING INSTRUCTIONS
IMPORTANT
IT  IS  RECOMMENDED  THAT A  QUALIFIED  SERVICE  TECHNICIAN 
PERFORM THE INITIAL FIRING OF THE HEATER. AT THIS TIME THE 
USER SHOULD ASK THE TECHNICIAN ANY QUESTIONS IN REGARD 
TO THE OPERATION AND MAINTENANCE OF THE UNIT.
 
CAUTION
BEFORE PROCEEDING WITH THE OPERATION OF THE UNIT, MAKE 
SURE HEATER AND SYSTEM ARE FILLED WITH WATER AND ALL AIR 
IS EXPELLED FROM HEATER AND PIPING.
NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS 
FILLED WITH WATER AND A TEMPERATURE AND A PRESSURE RELIEF 
VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER. 
DO NOT ATTEMPT TO OPERATE HEATER WITH COLD WATER INLET 
VALVE CLOSED.
FILLING:
  1.  Close the heater drain valve.
  2.  Open a nearby hot water faucet to permit the air in the system to escape.
  3.  Fully open the cold water inlet pipe valve allowing the heater and piping 
to be filled.
  4.  Close the hot water faucet as water starts to flow.
  5.  The heater is ready to be operated.
THE MAIN MANUAL GAS SHUTOFF VALVE MUST HAVE BEEN CLOSED 
FOR AT  LEAST  FIVE  (5)  MINUTES.  THIS  WAITING  PERIOD  IS AN 
IMPORTANT SAFETY STEP. ITS PURPOSE IS TO PERMIT GAS THAT 
MIGHT  HAVE ACCUMULATED  IN THE  COMBUSTION  CHAMBER TO 
CLEAR. IF YOU DETECT GAS AT THE END OF THIS PERIOD, DO NOT 
PROCEED WITH LIGHTING. RECOGNIZE THAT GAS ODOR, EVEN IF 
IT SEEMS WEAK, MAY INDICATE THE PRESENCE OF ACCUMULATED 
GAS SOMEPLACE IN THE AREA WITH A RISK OF FIRE OR EXPLOSION. 
SEE THE FRONT PAGE FOR STEPS TO BE TAKEN.
DO NOT USE THIS HEATER IF ANY PART HAS BEEN UNDER WATER. 
IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT 
THE HEATER AND TO REPLACE ANY PART OF THE CONTROL SYSTEM 
AND ANY GAS CONTROL WHICH HAS BEEN UNDER WATER.
LIGHT  THE  UNIT  IN  ACCORDANCE  WITH  THE  OPERATING 
INSTRUCTIONS LABEL ATTACHED TO THE HEATER.  
THESE  INSTRUCTIONS ARE  REPEATED  IN  THE  LIGHTING AND 
OPERATING LABEL ILLUSTRATION ON PAGE 20 IN THIS MANUAL.
ADJUSTMENT PROCEDURE
INITIAL START-UP - (A)JWSH100150 MODEL
Main line gas pressure to the water heater for natural gas should be between 
a  maximum  of  10.5"  (2.59Kpa  for  natural  gas)  W.C.  (14.0"/3.45Kpa  for 
propane) and a minimum as shown in Table 4: that is, for Natural Gas, 4.8 
(1.18Kpa) W.C. and 8.5" (2.08Kpa) for Propane Gas. The inlet gas pressure 
must not exceed the maximum value. A service regulator must be installed 
within 10' (305 cm) of the unit.
  1.  Check gas line pressure with a manometer.
  2.  Check  manifold  pressure  (see Table  4,  page  20)  using  a  pressure  
      gauge  (manometer)  connected  to  the  manifold  pressure  tap  on  the  
      gas control valve.
  If  full  rate  adjustment  is  required,  remove  cover  screw  from  top  of  the  
  gas control valve.
Using a small screwdriver, turn adjusting screw clockwise 
 to increase  
or counterclockwise 
 to decrease gas pressure to obtain 4.0" (1 kPa) 
for natural gas and 10.0" W.C. (2.5  Kpa) for L.P. Gas.
  3.  Cycle the burner on and off several times to check its operation.
  4.  Check the operation of the limit and operating controls.
3600  
 X 1050 = 150,000 Btuh (44 Kw)
25.25