Sea Frost Bait Freezer Manual Do Utilizador

Página de 11
 
 
 
WARNING:  A clear sight glass can also indicate a completely EMPTY system.  Anytime 
the compressor is started, white foam should appear in the sight glass indicating that the 
refrigerant is present.  This foam may disappear quite quickly but, IF NO FOAM IS 
EVIDENT and the system is not cooling, the system is empty.  DO NOT OPERATE THE 
SYSTEM in this empty condition.  Operation in this mode will ruin the compressor.  Turn 
off the main breaker to the control panel to prevent operation until the system can be 
properly leak tested and recharged. 
 
 
Fast moving white foam with the compressor operating indicates an insufficient charge 
level.  Watch closely for a transition from foam to total liquid, (indicated by a clear sight 
glass).  This transition point can be missed if proper attention is not given.  Also, IT IS 
POSSIBLE for the sight glass to show large bubbles even when the charge is sufficient, 
so it is important to differentiate between "foam" and "bubbles".  The foam condition has 
velocity and direction; the bubbles are large, temporary, and nearly stationary. Do not 
try to chase away these larger bubbles with more refrigerant: overcharging will then 
occur.  Air in the system may give a false sight glass reading, which could lead to 
overcharging.  If in doubt, discharge a suspected overcharged system to continuous 
foam and slowly add refrigerant to clear the glass.  MONITOR THE SIGHT GLASS 
CONTINUALLY since the glass will not indicate when the system is overcharged. 
 
In a warm system, when the cabinet is above freezing (32.F) upon start-up, the sight 
glass may take several minutes to clear.  A cold cabinet may show a clear glass within 
seconds of start-up. 
 
                                                         
TROUBLESHOOTING 
 
The low side operating pressure of the system will not indicate the amount of 
refrigerant in the system.  The valve will not give proper operation or pressure if it is 
undercharged. Check the valve scribe line.  It should correlate to gauge pressure. 
 
The system requires enough refrigerant to supply liquid to the valve.  If the valve has a 
steady hissing sound then the charge is ok.  If the valve is sputtering then it is low.  If 
the valve is making a noticeable roar it is empty.  If the low side pressure is properly set 
the high side pressure will be 80 to 135 psi depending on the air temperature (50 to 95 
degrees F.) at the unit.  Almost immediately upon start up the valve body will begin to 
frost. 
 
Do not add refrigerant charge to a pre-charged system.    
Maximum charge 12 oz. R-134a