Dacor DHW361 Guia Da Instalação

Página de 16
4
Recirculating Configuration
Recirculating kits AVDH1 and AVDH2 contain the parts 
necessary to convert a DHW series hood to a recircu-
lating configuration in instances where exhausting the 
hood outside the building is not practical or desired. The 
kit consists of a top cap and charcoal filter(s). When 
installed, the top cap redirects air flow out the vents in the 
sides of the hood chimney assembly. The provided char-
coal filter(s) is/are installed underneath the mesh type 
filter(s) included with the hood. The charcoal filter reduces 
smoke and fumes before the hood exhaust is vented into 
the room. Use kit AVDH1 for models DHW301, DHW361 
and DHW421. Use kit AVDI2 for model DHW482.
Ducted Installation - Planning 
and Installing the Duct Work
 WARNING
•  To prevent combustion by-products, smoke or odors 
from entering the home and to improve efficiency, 
tape all duct joints securely.
•  Use only duct work deemed acceptable by state, 
municipal and local codes.
• 
DO NOT install an additional in-line or external 
blower to increase the length of the duct run. Even 
small differences between blower air flow rates can 
greatly reduce the air draw of the hood.
 CAUTION
To reduce the risk of fire and to properly exhaust air, be 
sure to duct air outside the house or building. Do not 
vent exhaust air into spaces within walls or ceilings or 
into attics, crawl spaces or garages.
Installation Specifications
 
■ All duct work materials (including screws and duct 
tape) must be purchased separately by the customer. 
 
■ When planning new 
duct work, always 
look for the shortest, 
most direct route to 
the outside. Venting 
can be done through 
the roof or directly 
through the back 
wall to the outside as 
shown.
 
■ Local building codes 
may require the use 
of makeup air systems with ventilation systems that 
move air greater than the specified movement rate 
(CFM). The specified rate varies based on locale. 
Consult a qualified HVAC specialist when designing 
the system for the requirements in your area and to 
assure optimal performance.
 
■ The hood exhaust connects to an 8-inch round duct. 
You can increase the duct size over the duct run if 
desired. To prevent a back draft, never decrease the 
duct size over the run. If existing duct work is smaller 
than 8 inches in diameter, remove it and replace it 
with 8-inch duct work.
 
■ Do not rely on tape alone to seal duct joints. Fasten 
all connections with sheet metal screws and tape all 
joints with certified silver tape or duct tape. Use sheet 
metal screws as required to support the duct weight.
 
■ To prevent back-drafts, a damper at the duct outlet 
may  also be required.
 
■ Make sure duct work does not interfere with floor 
joists  or wall studs.
Calculating the Maximum Duct Run Length
The maximum straight duct length for the hood is 50 feet. 
To determine the actual maximum duct run, subtract the 
equivalent length of each elbow, transition and cap from 
50 feet.
EQUIVALENT LENGTHS 
Piece
Subtract
Piece
Subtract
8” 90° elbow
7 feet
10” 90° elbow
5 feet
8” 45° elbow
3 feet
10” 45° elbow
2 feet
3¼” X 10”
to round 90° 
transition
25 feet
3¼” X 10” to
8”/10” round 
transition
4 feet
Roof cap
*
Wall cap with 
damper
*
* The equivalent lengths of roof and wall caps vary with 
model and configuration. For equivalent length, contact 
the manufacturer or a qualified HVAC specialist.
Chimney
Top cap
Duct inside
chimney between
hood and top cap 
(not provided)