Movincool CLASSICPLUS14 Manual Do Serviço

Página de 66
Repair Section
37
Control 
panel 
display 
turns on
Control 
Panel 
display 
shows error 
codes.
1. Display code “FL”.
Drain tank (optional) is filled 
with the drain water.
Discharge the drain water.
Improper drain switch 
connection.
Check connection.
Defective drain switch.
Replace drain switch.
2. Display code “AS”.
Improper routing of drain 
hose.
Repair drain hose, then reset 
unit.
To RESET: Press ON/OFF 
and HI/LO buttons on the 
control box simultaneously 
for 5 sec.
Defective condensate pump. Repair or replace 
condensate pump, then reset 
unit.
To RESET: Press ON/OFF 
and HI/LO buttons on the 
control box simultaneously 
for 5 sec.
Missing jumper connector.
Connect jumper connector.
3. Display code “RT”.
Improper room thermistor 
connection.
Check connection.
Defective room thermistor 
(short or open).
Replace room thermistor.
4. Display code “FT”.
Improper freeze protection 
thermistor connection.
Check connection.
Defective freeze protection 
thermistor (short or open).
Replace freeze protection 
thermistor.
5. Display code “ALRM”.
Turn the input signal on and 
continue it.
1) Check external input 
signal.
2)  Reset the system.
To RESET: Press ON/OFF 
and HI/LO buttons on the 
control box simultaneously 
for 5 sec.
6. Display code “FZ”.
See “Stops after running a while” of Troubleshooting on
page 38.
Symptom
Possible Cause
Remedy
Checking Area
Cause