Repair Section
38
(3) Overflow of drain water
Symptom
Possible Cause
Remedy
Checking Area
Cause
Stops 
immediately 
after 
starting
Control 
panel 
display 
normally.
1. Fan on-off relay on the relay 
board.
Open circuit or insufficient 
contact.
Replace relay board.
2. Fan HI/LO change relay on 
the relay board.
Open circuit or insufficient 
contact.
Replace relay board.
3. Fan motor insulation 
resistance.
Insulation failure on fan 
motor.
Replace fan motor.
4. Compressor relay on the 
relay board.
Open circuit or insufficient 
contact.
Replace relay board.
5. Compressor insulation 
resistance.
Insulation failure on 
compressor.
Replace compressor.
Stops after 
running a 
while
Control 
panel 
display 
normally.
1. Temperature of fan motor 
(abnormally high).
Operation of safety device 
(IOLF) due to fan motor 
malfunction.
Replace fan motor.
2. Temperature of compressor 
(abnormally high).
Operation of safety device 
(IOLC) due to compressor 
malfunction.
Replace compressor.
3. Refrigerant leakage.
Insufficient refrigerant or gas 
leakage.
Repair and charge 
refrigerant.
4. Dirt on evaporator or 
condenser.
Insufficient cooling of 
evaporator or condenser.
Clean evaporator or 
condenser.
5. Duct connection state.
Improper connection.
Repair duct connection.
Symptom
Possible Cause
Remedy
Checking Area
Cause
Overflow from the unit.
1. Drain pan.
Cracks in drain pan.
Check and repair.
2. Water level in drain pan.
Clogged drain hose.
Check and replace.
3. Drain hole.
Reversed air flow from drain 
hole.
Insert a trap on discharge 
drain hose.
4. Clogged air filter.
Reversed air flow from drain 
hole due to the excessive 
negative pressure inside of 
the unit.
Clean air filter.