that of cooling mode. 
8.6.5  At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode. 
 
8.7 
  Heating mode 
8.7.1  Generally, the 4-way valve is open in  heating mode, but it is closed in  defrosting mode. 4-way 
valve must delay 2 minutes compared with compressor if the compressor changed into non-heating 
mode or turned off. 4-way valve doesn't delay in dehumidifying mode 
8.7.2  Generally, the outdoor fan is turned off with the on-off action of compressor in  heating mode, 
except for the defrosting mode or the end of defrost 
8.7.3  Action of compressor  and outdoor fan motor at heating mode:  compressor must run for 7 
minutes after starting and then judge temperature. Meanwhile other protections are still valid. 
Ts+2*
T
Room temp. up
Room temp. down
Ts+3*
Compressor and 
outdoor fan off
Compressor and 
outdoor fan on
Ts
 
* This parameter can be changed from 0 to 3 
8.7.4  Indoor Fan actions at heating mode 
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function 
prevails. 
Anti-cold wind control function at heating mode (T=indoor exchanger temp.) 
T
T temp. up
T temp. down
TE2
Setting fan speed
Fan off
Breeze
TE3
TE1
TE4
 
     
 
8.7.5  Auto wind at heating mode (T=indoor temp.)