Honeywell XL 800 SERIES Manual Do Utilizador

Página de 36
Description of the XCL8010AU Controller Module Excel 
800 
EN1B-0410GE51 R0908A 
 
10
Corresponding Terminal Sockets 
Table 6. I/O modules and corresponding terminal sockets 
I/O module 
socket 
scope of delivery 
XF821AU, 
XFL821AU 
XF822AU, 
XFL822AU, 
XFLR822AU, 
XFR822AU 
XS821-22 
1 terminal socket,  
1 bridge connector 
1 swivel label holder 
XF823AU, 
XFL823AU 
XS823 
1 terminal socket,  
1 bridge connector 
1 swivel label holder 
XF824AU, 
XFL824AU, 
XFLR824AU, 
XFR824AU 
XFR825AU 
XS824-25 
1 terminal socket,  
1 bridge connector 
1 swivel label holder 
1 long cross connector 
 
Interfaces and Bus Connections 
The Excel 800 System can be connected to the following 
devices and systems: 
 
Panel Bus 
•  For communication with up to 16 Panel Bus I/O modules 
• Polarity-insensitive 
 
LonWorks Bus 
•  For communication with other L
ON
W
ORKS
 Bus devices 
within the building 
•  FTT10, link power compatible 
• Polarity-insensitive 
 
C-Bus 
•  For communication with other controllers 
 
HMI 
•  For connecting an operator interface, e.g., XI582 or a 
laptop, e.g., for CARE 
 
Modem 
• NO CONNECTION 
 
Technical Data 
System Data 
Table 7. System data
 
Operating voltage 
24 VAC/DC, 60 Hz 
Power consumption 
Max. 3.57 A 
(1 XCL8010AU Controller 
+ 16 I/O modules) 
 
Operational Environment 
Table 8. Operational environment 
ambient operating 
temperature 
0 ─ 49 °C (32 ─ 122 °F) 
ambient operating 
humidity 
5 ─ 93 % rel. humidity  
(non-condensing) 
ambient storage 
temperature 
–20 ─ +70 °C (–4 ─ +158 °F) 
ambient storage 
humidity 
5 ─ 95 % rel. humidity  
(non-condensing) 
 
Smoke Control Configuration 
XL800
2
3
4
5
6
7
9
10
11
12
8
UL-LISTED
FIRE ALARM
CONTROL UNIT
SMOKE CONTROL CONFIGURATION
FIREFIGHTERS’
SMOKE CONTROL
PANEL (FSCS)
14505068
AUDIBLE
ANNUNCIATOR
STATUS CONTROL
VERIFICATION
DAMPER
AIRFLOW SENSOR
1
AO
AO
AO
SUPPLY
FAN
EXHAUST
FAN
 
Fig. 8. Typical smoke control configuration 
NOTES: 
1
  Locate and configure per NFPA 92A, Section 3-4.3.4. 
UL-listed annunciator / FSCS panel switches have a 
minimum rating of 24 V, 1/10 Amp, and lamps / LEDs 
have a rating of 24 V, limited to 50 mA. 
2
  Locate so as to minimize control wiring and piping. 
Avoid running wires or piping through areas that have 
a high fire risk. 
3
  Locate per UL 555S.