Connect XCL8010AU Controller Module and I/O modules
using the bridge connectors.
using the bridge connectors.
This provides power supply and communication connection.
No further wiring is necessary.
No further wiring is necessary.
Multiple Rails in Single Cabinet
The multiple rails of a controller system are connected in
series.
series.
►
Connect the rail ends as follows:
– Power supply
– Power supply
via power supply terminals 73, 74 or 77, 78
– Communication
via communication terminals 71, 72 or 75, 76
I/O MODULE
XCL8010AU
1 2
I/O MODULE
71
72
73
74
I/O MODULE
71
72
73
74
I/O MODULE
71
72
73
74
I/O MODULE
75
76
77
78
I/O MODULE
75
76
77
78
I/O MODULE
71
72
73
74
Fig. 10. Wiring the power supply and the communication
lines to the I/O modules
LonWorks Bus I/O Modules in Separate Rooms
In this scenario, only communication lines must be connected
between the rooms.
between the rooms.
►
Connect the last module of room 1 to the first module of
room 2:
– via communication terminals 71, 72 or 75, 76
room 2:
– via communication terminals 71, 72 or 75, 76
XCL8010AU
1 2
71
72
73
74
ROOM 2
ROOM 1
LonWorks
I/O MODULE
LonWorks
I/O MODULE
73
74
LonWorks
I/O MODULE
LonWorks
I/O MODULE
LonWorks
I/O MODULE
78
75
76
77
78
75
76
77
Fig. 11. Wiring the L
ON
W
ORKS
Bus I/O modules in
separate rooms
Maximum Cable Length
Max. cable length: 1200 meters (4000 ft), supervised.
How to Connect Panel Bus and L
ON
W
ORKS
Bus Mixed Controller Systems
Connecting I/O Modules
For connecting the I/O modules with each other, proceed as
described for single-bus controller systems.
described for single-bus controller systems.
Connecting I/O Modules to the XCL8010AU
Panel Bus I/O Modules
►
Connect communication terminals 71 ─ 74 or 75 ─ 78 of
Panel Bus I/O modules to communication terminals 71 ─
74 or 75 ─ 78 of the XCL8010AU Controller Module using
either
– Bridge connectors
Panel Bus I/O modules to communication terminals 71 ─
74 or 75 ─ 78 of the XCL8010AU Controller Module using
either
– Bridge connectors
for flush mounting on a single DIN rail or
– Cables
for separate mounting, e.g., on multiple rails, separate
cabinets, etc.
cabinets, etc.
L
ON
W
ORKS
Bus I/O Modules
►
Connect communication terminals 71 ─ 74 or 75 ─ 78 of
L
L
ON
W
ORKS
Bus I/O modules to L
ON
W
ORKS
terminals 11 ─
14 of the XCL8010AU using cables.