Honeywell XL 800 SERIES Manual Do Utilizador

Página de 36
Description of the XCL8010AU Controller Module Excel 
800 
EN1B-0410GE51 R0908A 
 
12
XCL8010AU, I/O Modules on Single Rail 
► 
Connect XCL8010AU Controller Module and I/O modules 
using the bridge connectors. 
This provides power supply and communication connection. 
No further wiring is necessary. 
 
Multiple Rails in Single Cabinet 
The multiple rails of a controller system are connected in 
series. 
► 
Connect the rail ends as follows: 
–  Power supply   
via power supply terminals 73, 74 or 77, 78 
–  Communication  
 
via communication terminals 71, 72 or 75, 76 
 
I/O MODULE
XCL8010AU
1 2
I/O MODULE
71
72
73
74
I/O MODULE
71
72
73
74
I/O MODULE
71
72
73
74
I/O MODULE
75
76
77
78
I/O MODULE
75
76
77
78
I/O MODULE
71
72
73
74
 
Fig. 10. Wiring the power supply and the communication 
lines to the I/O modules 
 
LonWorks Bus I/O Modules in Separate Rooms 
In this scenario, only communication lines must be connected 
between the rooms. 
► 
Connect the last module of room 1 to the first module of 
room 2: 
–  via communication terminals 71, 72 or 75, 76 
 
XCL8010AU
1 2
71
72
73
74
ROOM 2
ROOM 1
LonWorks
I/O MODULE
LonWorks
I/O MODULE
73
74
LonWorks
I/O MODULE
LonWorks
I/O MODULE
LonWorks
I/O MODULE
78
75
76
77
78
75
76
77
 
Fig. 11. Wiring the L
ON
W
ORKS
 Bus I/O modules in 
separate rooms 
 
Maximum Cable Length 
Max. cable length: 1200 meters (4000 ft), supervised. 
 
How to Connect Panel Bus and L
ON
W
ORKS
 
Bus Mixed Controller Systems 
Connecting I/O Modules 
For connecting the I/O modules with each other, proceed as 
described for single-bus controller systems. 
 
Connecting I/O Modules to the XCL8010AU 
Panel Bus I/O Modules 
► 
Connect communication terminals 71 ─ 74 or 75 ─ 78 of 
Panel Bus I/O modules to communication terminals 71 ─ 
74 or 75 ─ 78 of the XCL8010AU Controller Module using 
either 
–  Bridge connectors  
for flush mounting on a single DIN rail or 
– Cables  
for separate mounting, e.g., on multiple rails, separate 
cabinets, etc. 
 
L
ON
W
ORKS
 Bus I/O Modules 
► 
Connect communication terminals 71 ─ 74 or 75 ─ 78 of 
L
ON
W
ORKS
 Bus I/O modules to L
ON
W
ORKS
 terminals 11 ─ 
14 of the XCL8010AU using cables.