Honeywell XL 800 SERIES Manual Do Utilizador

Página de 36
Excel 800 
Mounting/Dismounting Modules 
 19 
EN1B-0410GE51 
R0908A 
C-Bus Tx LED and Rx LED 
The XCL8010AU
 
Controller Module is equipped with a Tx 
LED (status: yellow/OFF) and an Rx LED (status: 
yellow/OFF). 
 
1
C-Bus
2
 
Fig. 29. C-Bus Tx LED (1) and Rx LED (2) 
 
C-Bus LEDs 
Table 14. Controller C-Bus LEDs 
Tx (1) 
flickering 
The controller is sending data onto the  
C-Bus 
Rx (2) 
flickering 
The controller is receiving data from the  
C-Bus 
 
Reset Button 
The XCL8010AU
 
Controller Module is equipped with a reset 
button. 
 
1
RESET
 
Fig. 30. Reset button (1) 
 
Pushing the reset button (1), e.g. using a paperclip, will cause 
the XCL8010AU
 
Controller Module to reset. 
 
NOTE: 
In the event of a reset, all non-volatile memory 
contents are permanently deleted, though the 
clock will not be set to zero. In order to avoid 
problems, we therefore recommend that you 
always save your application changes (e.g., time 
program changes) to FLASH memory. 
 
HMI Interface 
The XCL8010AU
 
Controller Module is equipped with an HMI 
Interface for the connection of HMIs, e.g., XI582 Operator 
Interface or a laptop (with XL-Online/CARE). 
 
 
Fig. 31. HMI interface, Tx LED (1) and Rx LED (2) 
 
HMI interface LEDs on RJ45 socket 
Table 15. HMI interface LEDs 
Tx (1) 
flickering 
The controller is transmitting data to the HMI 
Rx (2) 
flickering 
The controller is receiving data from the HMI 
 
HMI interface Signals on RJ45 socket 
Table 16. Signals of the HMI interface 
pin 
signal type 
1 - 
2 Receive 
3 Transmit 
4 - 
5 Signal 
ground 
6 - 
7 5 
8 - 
 
NOTICE 
Equipment damage! 
► 
If earth grounding is required, make sure that only terminal 
2 is connected to earth ground. Terminal 1 must not be 
connected to earth ground. See also Appendix 1.