Honeywell XL 800 SERIES Manual Do Utilizador

Página de 36
Excel 800 
Mounting/Dismounting Modules 
 17 
EN1B-0410GE51 
R0908A 
 
Fig. 23. Locking the electronic module 
 
NOTE: 
The red locking mechanism will not close if the 
electronic module is not properly mounted. 
 
Dismounting Electronic Modules 
NOTE: 
Electronic modules can be removed from the 
socket or inserted into the sockets without 
switching off the power supply. The behavior of 
connected field devices must be taken into 
consideration. 
 
► 
Open the red locking mechanism by sliding it to the left 
and then gently pull the electronic module out of the 
terminal socket. 
 
 
Fig. 24. Dismounting the electronic module 
 
Connecting via C-Bus 
Via C-Bus, an XCL8010AU Controller Module can be 
connected to other controller systems to form a network. 
 
Connecting to the Controller 
► 
Connect the C-Bus to the XCL8010AU Controller Module 
as follows: 
–  Input to C-Bus terminals 8 and 9 
–  Output to C-Bus terminals 5 and 6 
–  Do not connect the C-Bus to the cabinet earth or any 
other earth ground points 
Setting the C-Bus Termination Switch 
► 
Set the C-Bus termination switch S1 appropriately. 
 
 
Fig. 25. C-Bus termination switch S1 
 
Table 11. XCL8010AU
 
C-Bus termination switch settings 
switch setting 
S1 
baud rate 
9.6k all 
Up to 9600 baud (default setting) 
76k mid 
Up to 76800 baud without bus termination  
76k end 
Up to 76800 baud with bus termination 
 
Shielding 
In principle, data transmitting cables should be shielded in 
case of RFI. 
► 
On the controller side, connect the shield to terminals 7 
and 10. 
► 
On the side of the device, connect the shield to the 
respective terminals. 
Do not connect it to the cabinet ground or any other 
ground points. 
 
Connecting HMIs or Laptops 
Laptops or HMIs, e.g., XI582, can either be connected via the 
HMI interface of the XCL8010AU Controller Module or via the 
L
ON
W
ORKS
 interface. 
 
Connecting the XI582 Operator Interface 
► 
Connect the XI582AH Operator Interface to the HMI 
interface or L
ON
W
ORKS
 interface of the XCL8010AU
 
Controller Module by means of 
–  the XW882 cable or 
–  the XW582 cable connected with an XW586 cable.