Excel 800 
Description of the I/O Modules 
 25 
EN1B-0410GE51 
R0908A 
Modules with Manual Overrides 
The XFR822AU/XFLR822AU Analog Output Modules are 
equipped with manual overrides: one rotary knob for each 
analog output. 
The manual overrides can be set manually to either "auto" or 
"0 ─ 110%". 
 
NOTICE 
Damage to the electronic module! 
► 
Do not use a tool to adjust the rotary knobs. 
► 
Do not use excessive force. Adjust only by hand. 
 
XFL822AU Connection Example 
XFL822AU
1
73
8
11
XSL511
L
N
Umax = 11 VDC
Imax = 1 mA, -1 mA
14507287
POWER
MODULE
GND SIGNAL 24VAC
M
24V
~
 
Fig. 40. XFL822AU Analog Output Module 
 
Synchronization Behavior of Analog Output Module 
Configured as Floating Output 
In order to regularly update the real actuator position with the 
calculated position and thus ensure that the actuator 
definitely reaches its end position, a synchronization process 
is performed by the Analog Output Module. 
During the synchronization process, the Analog Output 
Module will continue running for the configured runtime once 
it reaches the calculated end position. 
This updating (synchronization) is performed: 
•  If the calculated position of the actuator  
< lower synchronization threshold (2 %)  
= synchronization towards 0 % 
•  If the calculated position of the actuator  
> upper synchronization threshold (98 %) 
= synchronization towards 100 % 
•  Following any power-up or any reset