Honeywell XL 800 SERIES Manual Do Utilizador

Página de 36
Description of the I/O Modules 
Excel 800 
EN1B-0410GE51 R0908A 
 
26
Binary Input Modules 
Types of Binary Input Modules 
Table 30. Excel 800 Binary Input Modules 
type 
description 
housing 
XF823 
Panel Bus Binary Input Module 
light-gray 
XFL823 
L
ON
W
ORKS
 Bus Binary Input 
Module 
dark-gray 
XS823 terminal 
socket 
light-gray 
 
Features 
•  12 binary inputs 
•  12 configurable status LEDs (green/red, yellow/OFF) 
•  Binary inputs can be used as 
–  Static digital inputs as dry-contacts 
 
 
Fig. 41. XF823AU Binary Input Module with terminal 
socket 
Legend 
 1  Service button S1 
  2  Hex switch S2 
 3  Input LEDs 
 4  Service LED 
 5  Power LED 
 
Functionality of service LED and power LED: see Table 42 
and following. 
 
Terminals 
BI12
12
25 26
74
78
73
77
72
76
71
75
24
V~
24
V~
24
V~0
24
V~0
COM
B
COM
B
COM
A
COM
A
BI11
11
BI10
10
BI9
9
BI8
8
BI7
7
BI6
6
BI5
5
BI4
4
BI3
3
BI2
2
BI1
1
24
23
22
21
20
19
18
17
16
15
14
GND
13
GND GND GND GND GND GND GND GND GND GND GND
 
Fig. 42. Terminal assignment and internal connections of 
Binary Input Modules 
 
Table 31. Description of Binary Input Module terminals 
ter-
minal 
signal 
comment 
71, 75
COM a 
2-wire communication bus (LON/Panel 
Bus) 
72, 76
COM b 
2-wire communication bus (LON/Panel 
Bus) 
73, 77
24 V~ 
Power supply 
74, 78
24 V~0 
Power supply 
1 ─ 12 BI1 ─ BI12 Binary inputs 1 ─ 12 
13 ─ 
24 
GND 
Ground. All grounds are connected 
internally to each other. 
25, 26
 
Shield connection (functional earth), 
internally connected to the DIN rail. 
 
NOTE: 
Shield connection to be used for shielded I/O 
cables only. It is not allowed to connect a 
L
ON
W
ORKS
 shield. 
 
Technical Data 
Table 32. Technical data for of Binary Input Modules 
input type 
dry-contact 
current rating (closed 
input) 
2 mA 
open contact voltage 
16 ─ 22 VDC