Honeywell XL 800 SERIES Manual Do Utilizador
Excel 800
Description of the I/O Modules
29
EN1B-0410GE51
R0908A
Table 34. Description of Relay Output Module terminals
terminal
signal
comment
71, 75
COM a
2-wire communication bus
(LON/Panel Bus)
(LON/Panel Bus)
72, 76
COM b
2-wire communication bus
(LON/Panel Bus)
(LON/Panel Bus)
73, 77
24 V~
Power supply
74, 78
24 V~0
Power supply
11
REL1 N.O.
Relay 1 N.O. contact
12
REL1 N.C.
Relay 1 N.C. contact
13
R1 COM
relay 1 common contact
14
R1 COM
For connection of relay 1 common via
cross connector*
cross connector*
21
REL2 N.O.
Relay 2 N.O. contact
22
REL2 N.C.
Relay 2 N.C. contact
23
R2 COM
Relay 2 common contact
24
R2 COM
For connection of relay 2 common via
cross connector*
cross connector*
31
REL3 N.O.
Relay 3 N.O. contact
32
REL3 N.C.
Relay 3 N.C. contact
33
R3 COM
Relay 3 common contact
RELAY B
L
OCK
1
34
R3 COM
For connection of relay 3 common via
cross connector*
cross connector*
41
REL4 N.O.
Relay 4 N.O. contact
42
REL4 N.C.
Relay 4 N.C. contact
43
R4 COM
Relay 4 common contact
44
R4 COM
For connection of relay 4 common via
cross connector*
cross connector*
51
REL5 N.O.
Relay 5 N.O. contact
52
REL5 N.C.
Relay 5 N.C. contact
53
R5 COM
Relay 5 common contact
54
R5 COM
For connection of relay 5 common via
cross connector*
cross connector*
61
REL6 N.O.
Relay 6 N.O. contact
62
REL6 N.C.
Relay 6 N.C. contact
63
R6 COM
Relay 6 common contact
RELAY B
L
OCK
2
64
R6 COM
For connection of relay 6 common via
cross connector*
cross connector*
25
Shield connection (functional earth),
internally connected to the DIN rail
internally connected to the DIN rail
* Do not connect by wire!
Permissible Loads
Table 35. Permissible loads of Relay Output Modules
max. load
per relay output
module (total)
(common)
module (total)
(common)
24 VAC, 60 Hz
12 A
24 VDC
12 A resistive, 12 A, 0.6 PF
12 A
24 VDC
12 A resistive, 12 A, 0.6 PF
per normally open
contact (common)
contact (common)
24 VAC, 60 Hz
4 A
24 VDC
4 A resistive, 4 A, 0.6 PF
4 A
24 VDC
4 A resistive, 4 A, 0.6 PF
per normally
closed contact
(common)
closed contact
(common)
24 VAC, 2 A, 60 Hz
24 VDC
4 A resistive, 4 A, 0.6 PF
24 VDC
4 A resistive, 4 A, 0.6 PF
Status LEDs with Manual Overrides
1
2
3
4
5
6
Honeywell
--1
--0
--AUTO
--AUTO
!
Fig. 46. Manual overrides (toggle switches)
The XFR824AU and XFLR824AU Relay Output Modules are
equipped with six manual overrides: one for each relay
output. These toggle switches can manually be set to either
"auto" or "0" or "1".
equipped with six manual overrides: one for each relay
output. These toggle switches can manually be set to either
"auto" or "0" or "1".
Table 36. Relay Output Module status LED behavior
mode
LED
N.O.*
(direct)
N.C.*
(reverse)
automatic mode, state
“logical ON”
“logical ON”
ON ON
OFF
automatic mode, state
“logical OFF”
“logical OFF”
OFF OFF
ON
override mode (setting “0”)
flashes
OFF
ON
override mode (setting “1”)
flashes
ON
OFF
*As configured during engineering.