Honeywell XL 800 SERIES Manual Do Utilizador

Página de 36
Description of the I/O Modules 
Excel 800 
EN1B-0410GE51 R0908A 
 
28
Relay Output Modules 
Types of Relay Output Modules 
Table 33. Excel 800 Relay Output Modules 
type 
description 
housing 
XF824 
Panel Bus Relay Output Module  light-gray 
XFR824 
Panel Bus Relay Output Module 
with manual overrides 
light-gray 
XFL824 
L
ON
W
ORKS
 Bus Relay Output 
Module 
dark-gray 
XFLR824 
L
ON
W
ORKS
 Bus Relay Output 
Module with manual overrides 
dark-gray 
XS824-25 
terminal socket; can be fitted 
with long (red) cross connector 
(incl. in scope of the delivery) 
light-gray 
 
Features 
•  6 relays (changeover contacts), arranged in two blocks 
•  XFLR824AU, XFR824AU: 6 manual overrides 
•  Low and line voltage allowed, see WARNING. 
 
 
Fig. 44. XF824AU Relay Output Module with terminal 
socket 
Legend 
 1  Service button S1 
  2  Hex switch S2 
 3  Manual overrides 
 4  Status LEDs 
 5  Service LED 
 6  Power LED 
Functionality of service LED and power LED: see Table 42 
and following. 
Terminals 
31
41
51
61
32
42
52
62
33
43
53
63
34
44
54
64
NO
NC
COM
CON
NO
NC
COM
CON
11
12
13
14
21
22
23
24
25
NO
NC
COM
CON
NO
NC
COM
CON
NO
NC
COM
CON
NO
NC
COM
CON
Relay block 2
74
78
73
77
72
76
71
75
24
V~
24
V~
24
V~0
24
V~0
COM
B
COM
B
COM
A
COM
A
Cross connector (can be removed, as desired)
Relay block 1
 
Fig. 45. Terminal assignment and internal connections of 
Relay Output Modules