Wiring 
Excel 800 
EN1B-0410GE51 R0908A 
Wiring 
All wiring to the XL800 controller is unsupervised, except as 
noted. 
All circuits are power limited, except for AC power circuits, 
relay contacts and other circuits as noted. 
All field wiring terminals accept 24 AWG to 14 AWG 
(0.25 mm
2
 to 2 mm
2
) conductors except as noted. 
All wiring must conform to local codes, ordinances, and 
regulations. Refer to job drawings for details. 
Verify that the voltage difference between any conductor and 
earth ground does NOT exceed 150 Vac. 
1.  Connect input/output device wiring, C-Bus transmission 
wiring (minimum 18 gage [0.8012 sq mm]), LON Bus 
transmission wiring, and 14507063 Power Cable to 
Controller per job drawings. Fig. 2 and Fig. 3 show typical 
controller wiring. Four Power Module models are available 
(see Table 2). 
2.  Connect line voltage to Terminals H and N of the 
14507287 Power Module. Connect a good earth ground to 
Terminal G of the Power Module. Fig. 5 through Fig. 7 
show typical power wiring. 
3.  For Power Modules -001 through -007, leave power to 
Power Supply and Controller OFF. Connect 14507063 
Power Cable from Controller to Power Module. 
 
  WARNING 
Risk of electric shock or equipment damage! 
► 
Subpanel and Controller power must remain OFF until 
Controller is checked. 
 
4.  Install optional Tamper Switch on cabinet per instructions 
in the cabinet installation instructions. Wire Tamper 
Switch per job drawings. 
5.  Mount cabinet door.
 
 
CAUTION 
Risk of electric equipment damage! Excessive static can 
burn out equipment. 
► 
Observe proper anti-static material handling practices 
when installing or servicing PC parts and related 
components. 
► 
Observe proper equipment and body grounding practices. 
► 
Discharge static electricity from your body before handling 
parts. 
 
Table 1. Connector terminal specifications 
connector terminal  pin  signal type 
input / 
output 
voltage 
type 
max. 
voltage 
max. current 
max. 
frequency 
max. line 
impedance 
analog input 
 
AI 
input 
SIGNAL  ±12 V 
±20 mA 
9600 baud 
8K ohms 
digital input 
 
DI 
input 
SIGNAL  ±10 V 
±20 mA 
-- 
15K ohms 
analog output 
 
AO 
output
(1
 
SIGNAL  ±10 V 
±20 mA 
9600 baud 
8K ohms 
digital output 
 
DO 
output
(2
 
AC/DC 
±24 VAC/DC ±50 mA 
-- 
10K ohms 
totalizer output 
 
TI 
input 
SIGNAL  ±12 V 
±12 mA 
100 Hz 
 
signal 
ground 
 
GND 
-- -- 
-- -- 
-- -- 
J1 RS-485 (C-BUS)
 (3
  1 
+A 
input / output SIGNAL  ±5 V 
1 mA / 180 mA 
9600 baud 
100 ohms 
 
-A 
input / output SIGNAL  ±5 V 
1 mA / 180 mA 
9600 baud 
100 ohms 
 
3S 
Shield 
-- -- 
-- -- 
-- -- 
(1
 special application; 
(2
 regulated; 
(3
 supervised 
 
Table 2. Power module models 
transformer max. input 
model 
Vac 
current draw 
Hz 
(48 VA) controller 
VAC output 
accessory output 
convenience outlet
14507287-001  120 
0.5 A 
60 
24 
 
120 Vac, 10A 
14507287-002  120 
1.7 A 
60 
24 
24 Vac, 100 VA, 24 Vac, 40 VA 
120 Vac, 10A 
14507287-003  120 
1.7 A 
60 
24 
24 Vac, 100 VA, 24 Vdc, 600 mA 
120 Vac, 10A 
14507287-007 120 
120 A 
60 
24 
-- 
--