Sanyo KH3072R / CH3072R Manual Do Utilizador

Página de 180
1
2
3
4
5
6
I-3
SM831148
1. Specifications
1-1 Unit Specifications
Wall-Mounted Type
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB
Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
Indoor Unit
KH2672R
Outdoor Unit
CH2672R
POWER SOURCE
230 - 208 V / 1 Phase / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity * [minimum~muximum] 
BTU / h
25,200 [9,500~25,200]
29,200 [8,000~29,200]
(17˚F)**
BTU / h
17,200
Moisture removal (High) 
Pints / h
8.1
Air circulation (H / M / L) 230 V 
CFM
559 / 475 / 390
External Static Pressure
in. WG
S.E.E.R. / H.S.P.F. (Region 4)
BTU / Wh
14.9
10.2
ELECTRICAL RATINGS
 
Voltage rating
V
230
208
230
208
Available voltage range
V
VAC 187 - 253
VAC 187 - 253
Max. Running amperes*
A
15.3
16.9
14.0
15.5
Power input
W
2,840
2,840
2,620
2,620
(17˚F)**
W
2,030
2,030
Back-up Heater
kW
Maximum overcurrent protection   (Indoor/Outdoor)
A
15 / 30
Low ambient control 
Built-in 0˚F
Fan speeds Indoor / Outdoor
3 and Automatic control / Variable
Optional Wired Remote Controller 
Optional Wireless Remote Controller
RCS-SH1UA  /  RCS-BH80UA. WL  
Air deflection (Horizontal / Vertical )
 / Automatic (Vertical )
Air filter
Washable
Drain pump (Drain connection)
  (20A , OD26mm)
Compressor
Rotary(SANYO)
Operation sound
Indoor - Hi/Me/Lo
dB - A
48 / 42 / 38
Outdoor - Hi
dB - A
49
Refrigerant control
Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length
ft. (m)
165 (50)
Limit of tubing length at shipment
ft. (m)
10~100 (3~30)
Limit of elevation difference
ft. (m)
Outdoor unit is higher than indoor unit : 100 (30)
between the two units
ft. (m)
Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tube
Narrow tube
in. (mm)
 3 / 8 (6.35)
outer diameter
Wide tube
in. (mm)
 5 / 8 (15.88)
Refrigerant amount at shipment
lbs. (kg) 
4.19 (1.9) - R410A 
DIMENSIONS & WEIGHT
Indoor unit 
Outdoor unit
Unit dimensions
Height
in. (mm)
12- 63/64 (330)
30- 23/32 (780) 
Width
in. (mm)
44- 7/8 (1,140)
37 (940)
Depth
in. (mm)
8- 31/32 (228)
13- 3/8 (340)
Package dimensions
Indoor unit 
Outdoor unit
Height
in. (mm)
15- 11/32 (390)
34- 31/32 (888)
Width
in. (mm)
47- 27/32 (1,215)
39- 31/32 (1,015)
Depth
in. (mm)
11- 17/32 (293)
16- 3/32 (409)
Net weight
lbs. (kg) 
40 (18)
128 (58)
Shipping weight
lbs. (kg) 
44 (20)
148 (67)
Shipping volume
cu.ft. (m 3 )
4.9 (0.139)
13.0 (0.369)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
FEATURES
MODEL No.
Controls
Microprocessor
RCS-SH80UG / RCS-TM80BG