Napoleon Fireplaces BGD42 Manual Do Utilizador

Página de 28
28
W415-0381 / H / 12.07.07
W h i t e   /   g r e y   f i l m 
forms.
Sulphur from fuel is being depos-
ited on glass, logs or combustion 
chamber surfaces.
-  clean the glass with a recommended gas fi replace glass cleaner. DO NOT 
CLEAN GLASS WHEN HOT. 
If deposits are not cleaned off regularly, the glass may become permanently 
marked.
Main burner fl ame is 
a blue, lazy, transpar-
ent fl ame.
Blockage in vent.
-  remove blockage. In extremely cold conditions, ice buildup may occur on the 
terminal and should be removed as required.
-  refer to Figure 23 to ensure correct location of storm collars.
Incorrect installation.
-  check that the logs are correctly positioned.
-  open air shutter to increase the primary air.
-  check the input rate: check the manifold pressure and orifi ce size as specifi ed 
by the rating plate values.
- check that the door gasketing is not broken or missing and that the seal is 
tight.
- check that both 5" and 8" vent liners are free of holes and well sealed at all 
joints.
- check that minimum rise per foot has been adhered to for any horizontal 
venting.
Carbon is being de-
posited on glass, logs 
or combustion cham-
ber surfaces.
Flame is impinging on the logs 
or combustion chamber.
Air shutter has become blocked
-  ensure air shutter opening is free of lint or other obstructions.
Remote wall switch is 
in "OFF" position; main 
burner comes on when 
gas knob is turned to 
"ON" position.
Wall switch is mounted upside 
down
- reverse.
Faulty valve.
- replace.
- replace.
Remote wall switch is ground-
ing.
- check for ground (short); repair ground or replace wire.
Remote wall switch wire is 
grounding.
Flames are very ag-
gressive.
- fi t door assembly into the lower support brackets and secure the four door 
latches.
Door is ajar
Venting action is too great.
-restrict vent exit with restrictor plate, W500-0205.
SYMPTOM
PROBLEM
TEST SOLUTION