“B” Group: Fine Tuning Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–38
NOTE: Parameter setting B032 affects the inverter’s electronic thermal protection 
(B012 setting) and its overload restriction function (B022 setting).
NOTE: For low B032 values, the effect on the electronic thermal protection and 
overload restriction functions may not be accurate.
B080: [AM] analog signal gain – This parameter allows you to scale the analog output 
[AM] relative to the monitored variable.
B082: Start frequency adjustment – When the inverter starts to run, the output 
frequency does not ramp from 0Hz. Instead, it steps directly to the start frequency 
(B082), and the ramp proceeds from upward there.
B083: Carrier frequency adjustment – The internal switching frequency of the 
inverter circuitry (also called the chopper frequency). It is called the carrier frequency 
because the lower AC output frequency of the inverter “rides” the carrier. The faint, 
high-pitched sound you hear when the inverter is in Run Mode is characteristic of 
switching power supplies in general. The carrier frequency is adjustable from 2.0 kHz to 
14 kHz. The audible sound decreases at the higher frequencies, but RFI noise and 
leakage current may be increased. Refer to the specification derating curves in Chapter 1 
to determine the maximum allowable carrier frequency setting for your particular 
inverter and environmental conditions.
NOTE: The carrier frequency setting must stay within specified limits for inverter-motor 
applications that must comply with particular regulatory agencies. For example, a 
European CE-approved application requires the inverter carrier to be less than 5 kHz.
B084, B085: Initialization codes – These functions allow you to restore the factory 
default settings. Please refer to 
B086: Frequency display scaling – You can convert the output frequency monitor on 
D001 to a scaled number (engineering units) monitored at function D007. For example, 
the motor may run a conveyor that is monitored in feet per minute. Use this formula:
 
Scaled output frequency (D_07)
Output frequency (D_01) Factor (B_86)
×
=