Hitachi L200 Manual Do Utilizador

Página de 280
L200 Inverter
Conf
igur
ing
Dr
iv
e P
a
ra
m
e
ters
3–39
“B” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
B032 Reactive current setting
Calibrate detection of motor’s 
reactive (no load) current for 
current monitor, electric 
thermal setting, and overload 
restriction setting.
Range is 50 to 200%
100.
100.
%
Io-SET    00100%
B080 [AM] analog signal 
gain
Adjust of analog output at 
terminal [AM],
range is 0 to 255
100.
100.
AM-Adj    00100%
B082 Start frequency adjust-
ment
Sets the starting frequency for 
the inverter output, range is 0.5 
to 9.9 Hz
0.5
0.5
Hz
fmin    0000.5Hz
B083 Carrier frequency 
setting
Sets the PWM carrier (internal 
switching frequency), range is 
2.0 to 14.0 kHz
5.0
5.0
kHz
Carrier   0005.0
B084 Initialization mode 
(parameters or trip 
history)
Select the type of initialization 
to occur, two option codes:
00... Trip history clear
01... Parameter initialization
02... Trip history clear and 
parameter initialization
00
00
INIT Mode    TRP
B085 Country code for initial-
ization
Select default parameter values 
for country on initialization, 
four options, option codes:
00... Japan version
01... Europe version
02... US version
01
02
INIT Slct     USA
B086 Frequency scaling 
conversion factor
Specify a constant to scale the 
displayed frequency for D007 
monitor, range is 0.1 to 99.9
1.0
1.0
Cnv Gain  0001.0
B087 STOP key enable
Select whether the STOP key 
on the keypad is enabled, two 
option codes:
00... enabled
01... disabled
00
00
STP Key      ON