B089: Monitor display select for networked inverter – When the L200 inverter is 
controlled via network, the inverter’s keypad display can still provide Monitor Mode. 
The D00x parameter selected by function B089 will be displayed on the keypad. See 
 for more details.
“B” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
B088 Restart mode after FRS
Selects how the inverter 
resumes operation when the 
free-run stop (FRS) is 
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency 
detected from real speed of 
motor (frequency matching)
00
00
RUN FRS      ZST
B089 Monitor display select 
for networked inverter
Selects the parameter 
displayed on the keypad 
display when the inverter is 
networked, 7 options:
01... Output frequency monitor
02... Output current monitor
03... Rotation direction 
monitor
04... Process variable (PV), 
PID feedback monitor
05... Intelligent input terminal 
status
06... Intelligent output terminal 
status
07... Scaled output frequency 
monitor
01
01
PANEL d001
B091 Stop mode selection
Selects how the inverter stops 
the motor, two option codes:
00... DEC (decelerate and stop)
01... FRS (free run to stop)
00
00
STP Slct     DEC
B130 Over-voltage 
LADSTOP enable
Pauses deceleration ramp when 
DC bus voltage rises above 
threshold level, in order to 
avoid over-voltage trip.
Two option codes:
00... Disable
01... Enable
00
00
OVLADSTOP    OFF
B150 Carrier mode
Automatically reduces the 
carrier frequency as the 
ambient temperature increases.
Two option codes:
00... Disable
01... Enable
00
00
Cr-DEC       OFF