“H” Group: Motor Constants Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–56
“H” Group: Motor Constants Functions
The “H” Group parameters configure the 
inverter for the motor characteristics. You 
must manually set H003 and H004 values to 
match the motor. Parameter H006 is factory-
set. If you want to reset the parameters to the 
factory default settings, use the procedure in 
control algorithm as shown in the diagram.
Output
A44
V/f control,
constant torque
V/f control,
variable torque
00
01
Inverter Torque Control Algorithms
“H” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
H003 Motor capacity
Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
5.5 / 7.5 / 11
Specified by 
the capacity of 
each inverter 
model
kW
AUX K     0.4 kW
H203 Motor capacity, 2nd 
setting
Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
5.5 / 7.5 / 11
kW
2AUXK     0.4 kW
H004 Motor poles setting
Four selections:
2 / 4 / 6 / 8
4
4
poles
AUX P         4p
H204 Motor poles setting, 2nd 
motor
Four selections:
2 / 4 / 6 / 8
4
4
poles
2AUXP         4p
H006 Motor stabilization 
constant
Motor constant (factory set), 
range is 0 to 255
100
100
AUX KCD      100
H206 Motor stabilization 
constant, 2nd motor
Motor constant (factory set), 
range is 0 to 255
100
100
2AUXKCD      100