Hitachi L200 Manual Do Utilizador

Página de 280
“C” Group: Intelligent Terminal Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–54
Output Logic and Timing
Logic Output Function – The inverter has a built-in logic output feature. You can select 
any two of the other nine intelligent output options for internal inputs. Then, configure 
the logic function to apply the logical AND, OR, or XOR (exclusive OR) operator as 
desired to the two inputs. The terminal symbol for the new output is [LOG]. Use C021, 
C022, or C026 to route the logical result to terminal [11], [12], or the relay terminals.
The following table shows all four possible logic input combinations with each of the 
three available logical operations.    
Input States
[LOG] Output State
A
B
AND
OR
XOR
0
0
0
0
0
0
1
0
1
1
1
0
0
1
1
1
1
1
1
0
C141
Logic function 
AND, OR, XOR
Input A
RUN, FA1, 
FA2, OL, 
OD, AL, Dc, 
FBV, NDc
Intelligent out-
puts used as 
internal inputs:
C142
Input B
RUN, FA1, 
FA2, OL, 
OD, AL, Dc, 
FBV, NDc
C143
12
11
AL1
AL0
AL2
C021
C022
C026
[LOG]
“C” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
C141 Input A select for logic 
output
9 programmable functions 
available for logic (discrete) 
outputs
00
00
LogicOut1    RUN
C142 Input B select for logic 
output
01
01
LogicOut2    FA1