Hitachi L200 Manual Do Utilizador

Página de 280
L200 Inverter
Oper
ations
and Monitor
ing
4–9
Using Intelligent Input Terminals
Terminals [1], [2], [3], [4], and [5] are identical, programmable inputs for general use. 
The input circuits can use the inverter’s internal (isolated) +24V field supply or an 
external power supply. This section describes input circuits operation and how to 
connect them properly to switches or transistor outputs on field devices.
The L200 inverter features selectable sinking or sourcing inputs. These terms refer to the 
connection to the external switching device—it either sinks current (from the input to 
GND) or sources current (from a power source) into the input. Note that the sink/source 
naming convention may be different in your particular country or industry. In any case, 
the just follow the wiring diagrams in this section for your application.
The inverter has a DIP switch for config-
uring the choice of sinking or sourcing 
inputs. To access it, you must remove the 
front cover of the inverter housing. In the 
figure to the right, the SR/SK switch 
(“source/sink switch”) is shown as 
located on the circuit board, at the right 
end of the logic signal connector.
DO NOT confuse it with the two, larger 
configuration switches nearby. The circuit 
board has the SR and SK markings above 
and below the switch as shown.
CAUTION: Be sure to turn OFF power to the inverter before changing the SR/SK 
switch position. Otherwise, damage to the inverter circuitry may occur.
[PCS] Terminal Wiring - The [PCS] 
terminal (Programmable Control System 
terminal) is named to include various 
devices that can connect to the inverter’s 
logic inputs. In the figure to the right, 
note the [PCS] terminal and the nearby 
diodes and DPDT switch. The upper part 
of the SR/SK switch selects between 
connecting the inverter’s +24V internal 
supply
 to [PCS] or allowing an external 
supply power to connect. The lower part 
of the SR/SK switch selects between 
connecting the input circuit common node 
to either Logic GND or the +24V supply.
The wiring diagrams on the following 
pages show the four combinations of 
using sourcing or sinking inputs, and 
using the internal or an external DC 
supply.
SR
SK
SR
SK
Legend:
Source
(default)
SR
SK
Sink
Logic inputs
1
2
3
4
5
L
PCS
L200
L
24V

SK
SR
SK
SR
PCS
Input 
circuits
1
5
Logic GND
Input common