Hitachi L200 Manual Do Utilizador

Página de 280
Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–24
Reset Inverter
The [RS] terminal causes the inverter to 
execute the reset operation. If the inverter is 
in Trip Mode, the reset cancels the Trip state. 
When the signal [RS] is turned ON and OFF, 
the inverter executes the reset operation. The 
minimum pulse width for [RS] must be 12 ms 
or greater. The alarm output will be cleared 
within 30 ms after the onset of the Reset command.
WARNING: After the Reset command is given and the alarm reset occurs, the motor 
will restart suddenly if the Run command is already active. Be sure to set the alarm reset 
after verifying that the Run command is OFF to prevent injury to personnel.
[RS]
Alarm
 signal
12 ms
minimum
t
1
0
approx. 30 ms
1
0
Option 
Code
Terminal 
Symbol
Function Name
Input 
State
Description
18
RS
Reset Inverter
ON
The motor output is turned OFF, the Trip Mode 
is cleared (if it exists), and powerup reset is 
applied
OFF
Normal power-ON operation
Valid for inputs:
C001, C002, C003, C004, 
C005
Required settings:
(none)
Notes:
When the control terminal [RS] input is already ON 
at powerup for more than 4 seconds, the remote 
operator display is “R-ERROR COMM<2>” (the 
display of the digital operator is –  –  –. However, 
the inverter has no error. To clear the digital 
operator error, turn OFF the terminal [RS] input 
and press one of the operator keys.
Pressing the Stop/Reset key of the digital operator can generate a reset operation only when an alarm 
occurs.
A terminal configured with the [RS] function can only be configured for normally open operation. The 
terminal cannot be used in the normally closed contact state.
When input power is turned ON, the inverter performs the same reset operation as it does when a pulse 
on the [RS] terminal occurs.
The Stop/Reset key on the inverter is only operational for a few seconds after inverter powerup when a 
hand-held remote operator is connected to the inverter.
If the [RS] terminal is turned ON while the motor is running, the motor will be free running (coasting).
If you are using the output terminal OFF delay feature (any of C145, C147, C149 > 0.0 sec.), the [RS] 
terminal affects the ON-to-OFF transition slightly. Normally (without using OFF delays), the [RS] 
input causes the motor output and the logic outputs to turn OFF together, immediately. However, when 
any output uses an OFF delay, then after the [RS] input turns ON, that output will remain ON for an 
additional 1 sec. period (approximate) before turning OFF.
Example (default input configurations 
shown—see page 
):
See I/O specs on page 
.
–FE
models
RS
1
2
3
4
5
L
PCS