Hitachi L200 Manual Do Utilizador

Página de 280
L200 Inverter
Oper
ations
and Monitor
ing
4–25
Thermistor Thermal Protection
Motors that are equipped with a thermistor can be protected from overheating. Input 
terminal [5] has the unique ability to sense a thermistor resistance. When the resistance 
value of the thermistor connected to terminal [TH] (6) and [L] is more than 3 k 
Ω ±10%, 
the inverter enters the Trip Mode, turns OFF the output to the motor, and indicates the 
trip status E35. Use this function to protect the motor from overheating
Option 
Code
Terminal 
Symbol
Function Name
Input 
State
Description
19
TH
Thermistor Thermal 
Protection
Sensor When a thermistor is connected to terminals [5] 
and [L], the inverter checks for over-temperature 
and will cause trip (E35) and turn OFF the 
output to the motor
Open
An open circuit in the thermistor causes a trip, 
and the inverter turns OFF the output
Valid for inputs:
C005 only
Required settings:
C085
Notes:
Be sure the thermistor is connected to terminals [5] 
and [L]. If the resistance is above the threshold the 
inverter will trip. When the motor cools down 
enough, the thermistor resistance will change 
enough to permit you to clear the error. Press the 
STOP/Reset key to clear the error.
Example (requires input configuration—
see page 
):
TH
thermistor
MOTOR
1
2
3
4
5
L
PCS