Force Operation from Digital Operator
This function permits a digital operator interface to override the following two settings 
in the inverter:
• A001 - Frequency source setting
• A002 - Run command source setting
When using the [OPE] terminal input, typically A001 and A002 are configured for 
sources other than the digital operator interface for the output frequency and Run 
command sources, respectively. When the [OPE] input is ON, then user has immediate 
command of the inverter, to start or stop the motor and to set the speed.
Option 
Code
Terminal 
Symbol
Function Name
Input 
State
Description
31
OPE
Force Operation 
from Digital 
Operator
ON
Forces the operator interface to override:
A001 - Frequency Source Setting, and
A002 - Run Command Source Setting
OFF
Parameters A001 and A002 are in effect again, 
for the frequency source and the Run command 
source, respectively
Valid for inputs:
C001, C002, C003, C004, 
C005
Required settings:
A001 (set not equal to 00)
A002 (set not equal to 02)
Notes:
When changing the [OPE] state during Run Mode 
(inverter is driving the motor), the inverter will stop 
the motor before the new [OPE] state takes effect.
If the [OPE] input turns ON and the digital operator 
gives a Run command while the inverter is already 
running, the inverter stops the motor. Then the 
digital operator can control the motor.