Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–32
ADD Frequency Enable
The inverter can add or subtract an offset value to the output frequency setting which is 
specified by A001 (will work with any of the five possible sources). The ADD 
Frequency is a value you can store in parameter A145. The ADD Frequency is summed 
with or subtracted from the output frequency setting only when the [ADD] terminal is 
ON. Function A146 selects whether to add or subtract. By configuring an intelligent 
input as the [ADD] terminal, your application can selectively apply the fixed value in 
A145 to offset (positively or negatively) the inverter output frequency in real time.   
A001
Function F001 setting
Control terminal
ModBus network input
Calculate function output
Keypad potentiometer
A145
 +
 +/–
ADD frequency
Frequency source setting
Output frequency setting
[ADD]
Intelligent input
A146 ADD direction select
Option 
Code
Terminal 
Symbol
Function Name
Input 
State
Description
50
ADD
ADD Frequency 
Enable
ON
Applies the A145 Add Frequency value to the 
output frequency.
OFF
Does not apply the Add Frequency. The output 
frequency retains its normal value.
Valid for inputs:
C001, C002, C003, C004, 
C005
Required settings:
A001, A145, A146
Notes:
A001 may specify any source; the Add Frequency 
will be added to or subtracted from that value to 
yield the output frequency value.
Example (requires input configuration—see 
page 
):
See I/O specs on page 
.
ADD
1
2
3
4
5
L