Using Intelligent Output Terminals
Oper
ations
and Monitor
ing
4–34
Using Intelligent Output Terminals
The intelligent output terminals are programmable in a similar way to the intelligent 
input terminals. The inverter has several output functions that you can assign individu-
ally to three physical logic outputs. Two of the outputs are open-collector transistors, and 
the third output is the alarm relay (form C – normally open and normally closed 
contacts). The relay is assigned the alarm function by default, but you can assign it to 
any of the functions that the open-collector outputs use.
Sinking Outputs,
Open Collector
Sinking Outputs,
Open Collector with
External Relays
L200 Inverter
12
11
CM2
Open collector outputs
Load
Load

+
Logic output 
common
The open-collector transistor 
outputs can handle up to 
50mA each. We highly recom-
mend that you use an external 
power source as shown. It 
must be capable of providing 
at least 100mA to drive both 
outputs at full load. To drive 
loads that require more than 
50mA, use external relay 
circuits as shown to the right.
L200 Inverter
12
11
CM2
Open collector outputs
Load
Load

+
Logic output 
common
If you need output current 
greater than 50mA, use the 
inverter output to drive a small 
relay. Be sure to use a diode 
across the coil of the relay as 
shown (reverse-biased) in 
order to suppress the turn-off 
spike, or use a solid-state 
relay.