L200 Series inverters have built-in RS-485 serial communications, featuring the 
ModBus RTU protocol. The inverters can connect directly to existing factory networks 
or work with new networked applications, without any extra interface equipment. The 
specifications for L200 serial communications are in the following table.
The network diagram below shows a series of inverters communicating with a host 
computer. each inverter must have a unique address, from 1 to 32, on the network. In a 
typical application, a host computer or controller is the master and each of the inverter(s) 
or other devices is a slave.
Item
Specifications
User-selectable
Transmission speed
4800 / 9600 / 19200 bps
Communication mode
Asynchronous
Character code
Binary
LSB placement
Transmits LSB first
Electrical interface
RS-485 differential transceiver
Data bits
8-bit (ModBus RTU mode)
(ASCII mode not
available)
Parity
None / even / odd
Stop bits
1 or 2 bits
Startup convention
One-way start from host device 
Wait time for response
0 to 1000 msec.
Connections
Station address numbers from 1 to 32
Connector
RJ45 modular jack
Error check
Overrun, Fleming block check code, 
CRC-16, or horizontal parity
L200
1
2
RUN
STOP
RESET
FUNC.
STR
HITACHI
POWER
ALARM
RUN
A
Hz
PRG
5 0.0
L200
1
2
RUN
STOP
RESET
FUNC.
STR
HITACHI
POWER
ALARM
RUN
A
Hz
PRG
5 0.0
L200
1
2
RUN
STOP
RESET
FUNC.
STR
HITACHI
POWER
ALARM
RUN
A
Hz
PRG
5 0.0
1
ModBus Network
2
32
Host computer