Hitachi L200 Manual Do Utilizador

Página de 280
L200 Inverter
Appendix B
B–3
Connecting the Inverter to ModBus
Follow the steps in this section to connect the inverter to the ModBus network.
1. Open Serial Port Cover - The inverter keypad has a hinged dust cover protecting the 
serial port connector. Lift the cover from the bottom edge, and tilt upward as shown 
(below left).
2. Modular Interconnect Removal - With the serial port cover opened, notice the RJ45 
modular connector behind it. Connect the serial cable and engage the locking tab in 
the connector as shown (below right).
3. Cable Wiring - The inverter communications 
port uses RS485 differential transceiver. The 
pinout is shown to the right and listed below. Be 
sure the cable connection you make matches the 
diagram.
Pin
Symbol
Description
1
Not used. Do not connect
2
Not used. Do not connect
3
Not used. Do not connect
4
Not used. Do not connect
5
SP
Send/Receive data Positive
6
SN
Send/Receive data Negative
7
Not used. Do not connect
8
Not used. Do not connect
RJ45 modular 
communications 
connector
Dust 
cover
Serial cable with RJ45 end