Hitachi L200 Manual Do Utilizador

Página de 280
L200 Inverter
Appendix B
B–5
6. Inverter Parameter Setup - The inverter has several settings related to ModBus 
communications. The table below lists them together. The Required column indicates 
which parameters must be set properly to allow communications. You may need to 
refer to the host computer documentation in order to match some of its settings.
NOTE: When you edit and store any of the parameters above, the inverter causes it to 
take effect immediately. ModBus transmission occurs only after you set the OPE/485 
DIP switch to the “485” position and turn on the inverter. Note that parameters C071 to 
C078 cannot be changed via the network. To edit them, reconnect the inverter keypad (or 
other digital operator) and edit the parameters.
Func.
Code
Name
Required
Settings
A001
Frequency source setting
00... Keypad potentiometer
01... Control terminal
02... Function F001 setting
03... ModBus network input
10... Calculate function output
A002
Run command source setting
01... Control terminal
02... Run key on keypad, or digital operator
03... ModBus network input
B089
Monitor display select for 
networked inverter
01... Output frequency monitor
02... Output current monitor
03... Rotation direction monitor
04... Process variable (PV), PID feedback 
monitor
05... Intelligent input terminal status
06... Intelligent output terminal status
07... Scaled output frequency monitor
C071
Communication speed selection
04... 4800 bps
05... 9600 bps
06... 19200 bps
C072
Node allocation
Network address, range is 1 to 32
C074
Communication parity selection
00... No parity
01... Even parity
02... Odd parity
C075
Communication stop bit selection
Range is 1 to 2
C076
Communication error select
00... Trip (error code E60)
01... Decelerate to a stop and trip (error code 
E60)
02... Disable
03... Free run stop (coasting)
04... Decelerate to a stop
C077
Communication error time-out
Comm. watchdog timer period,
range is 0.00 to 99.99 sec.
C078
Communication wait time
Time the inverter waits after receiving a 
message before it transmits.
Range is 0. to 1000. ms