ModBus Data Listing
Appendix B
B–38
C085
Thermistor input tuning
R/W Range is 0.0 to 200.0%
00EEh
0 to 2000
0.1 %
C086
[AM] terminal offset 
tuning
R/W Range is 0.0 to 10.0V
00C9h
0 to 100
0.1 V
C091
Debug mode enable
Displays debug parameters.
Two option codes:
00... Disable
01... Enable
C101
Up/Down memory 
mode
selection
R/W Controls speed setpoint for the 
inverter after power cycle. Two 
option codes:
00... Clear last frequency 
(return to default frequency 
F001)
01... Keep last frequency 
adjusted by UP/DWN
00CFh
0, 1
C102
Reset selection
R/W Determines response to Reset 
input [RST].
Three option codes:
00... Cancel trip state at input 
signal ON transition, stops 
inverter if in Run Mode
01... Cancel trip state at signal 
OFF transition, stops inverter if 
in Run Mode
02... Cancel trip state at input 
signal ON transition, no effect 
if in Run Mode
00D0h
0, 1, 2
C141
Input A select for logic 
output
R/W
See 
00EFh
0, 1, 2, 3, 
4, 5, 6, 7, 
8, 9
C142
Input B select for logic 
output
R/W
00F0h
C143
Logic function select
R/W Applies a logic function to 
calculate [LOG] output state, 
three options:
00...  [LOG] = A AND B
01... [LOG] = A OR B
02... [LOG] = A XOR B
00F1h
0, 1, 2
C144
Terminal [11] ON delay  R/W Range is 0.0 to 100.0 sec.
00F2h
0 to 1000
0.1 sec
C145
Terminal [11] OFF 
delay
R/W Range is 0.0 to 100.0 sec.
00F3h
0 to 1000
0.1 sec
C146
Terminal [12] ON delay
R/W Range is 0.0 to 100.0 sec.
00F4h
0 to 1000
0.1 sec
C147
Terminal [12] OFF 
delay
R/W Range is 0.0 to 100.0 sec.
00F5h
0 to 1000
0.1 sec
C148
Output relay ON delay
R/W Range is 0.0 to 100.0 sec.
00F6h
0 to 1000
0.1 sec
“C” Group Intelligent Terminal Functions
Func. 
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.