2–7
Basic System Description
A motor control system will obviously include a motor and inverter, as well as a breaker 
or fuses for safety. If you are connecting a motor to the inverter on a test bench just to get 
started, that’s all you may need for now. But a system can also have a variety of 
additional components. Some can be for noise suppression, while others may enhance 
the inverter’s braking performance. The figure and table below show a system with all 
the optional components you may need in your finished application.
NOTE: Note that some components are required for regulatory agency compliance (see 
Chapter 5 and Appendix D).
Thermal 
switch
Breaker, 
MCCB or 
GFI
From power supply
Motor
L1
L2
L3
+1
+
Inverter
GND
T1
T2
T3
Name
Function
Breaker /
disconnect
A molded-case circuit breaker (MCCB), ground fault 
interrupter (GFI), or a fused disconnect device. NOTE: 
The installer must refer to the NEC and local codes to 
ensure safety and compliance.
Input-side
AC Reactor
This is useful in suppressing harmonics induced on the 
power supply lines and for improving the power factor.
WARNING: Some applications must use an input-
side AC reactor to prevent inverter damage. See 
Warning on next page.
Radio noise filter
Electrical noise interference may occur on nearby 
equipment such as a radio receiver. This magnetic 
choke filter helps reduce radiated noise (can also be 
used on output).
EMI filter (for 
CE applications, 
see Appendix D)
Reduces the conducted noise on the power supply 
wiring between the inverter and the power distribution 
system. Connect to the inverter primary (input side).
Radio noise filter 
(use in non-CE 
applications)
This capacitive filter reduces radiated noise from the 
main power wires in the inverter input side.
DC link choke
Suppresses harmonics generated by the inverter. 
However, it will not protect the input diode bridge 
rectifier.
Radio noise filter
Electrical noise interference may occur on nearby 
equipment such as a radio receiver. This magnetic 
choke filter helps reduce radiated noise (can also be 
used on input).
Output-side
AC reactor
This reactor reduces the vibrations in the motor caused 
by the inverter’s switching waveforms, by smoothing 
the waveform to approximate commercial power 
quality. It is also useful to reduce harmonics when 
wiring from the inverter to the motor is more than 10m 
in length. 
LCR filter
Sine wave shaping filter for output side.