Hitachi L200 Manual Do Utilizador
Step-by-Step Basic Installation
In
v
e
rt
er Mounting
and Installation
2–18
Please use the terminal arrangement below corresponding to your inverter model.
NOTE: An inverter powered by a portable power generator may receive a distorted
power waveform, overheating the generator. In general, the generator capacity should be
five times that of the inverter (kVA).
power waveform, overheating the generator. In general, the generator capacity should be
five times that of the inverter (kVA).
CAUTION: Be sure that the input voltage matches the inverter specifications:
• Single/Three phase 200 to 240 V 50/60 Hz (up to 2.2kW) for NFEF/NFU models
• Three phase 200 to 240V 50/60Hz (above 2.2kW) for LFU models
• Three phase 380 to 480 V 50/60Hz for HFEF models
• Single/Three phase 200 to 240 V 50/60 Hz (up to 2.2kW) for NFEF/NFU models
• Three phase 200 to 240V 50/60Hz (above 2.2kW) for LFU models
• Three phase 380 to 480 V 50/60Hz for HFEF models
CAUTION: Be sure not to power a three-phase-only inverter with single phase power.
Otherwise, there is the possibility of damage to the inverter and the danger of fire.
Otherwise, there is the possibility of damage to the inverter and the danger of fire.
Inverter models L200–002NFEF/NFU, –004NFEF/NFU, –005NFEF
Inverter models L200–007NFEF to –022NFEF,
–037LFU, –004HFEF/HFU to –040HFEF/HFU
–037LFU, –004HFEF/HFU to –040HFEF/HFU
Jumper
Chassis
Ground
U/T1 V/T2 W/T3
Inverter models L200–055LFU, –075LFU, –055HFEF/HFU,
–075HFEF/HFU
–075HFEF/HFU
+
–
L1
L2 N/L3
+1
Jumper
Chassis
Ground
U/T1
+1
+
–
L1
L2 N/L3
L1
L2
L3
NFEF, NFU
LFU, HFEF, HFU
V/T2 W/T3
U/T1 V/T2 W/T3
Jumper
U/T1 V/T2 W/T3
Chassis
Ground
L3
+1
+
–
L1
L2