Hitachi L200 Manual Do Utilizador

Página de 280
L200 Inverter
In
v
e
rt
er Mounting
and Installation
2–27
If the Potentiometer Enable LED is OFF, follow the steps below.
Select the Keypad for the RUN Command - The RUN 
command causes the inverter to accelerate the motor to 
the selected speed. The Run command can arrive from 
various sources, including the control terminals, the Run 
key on the keypad, or the network. In the figure to the 
right, notice the Run Key Enable LED, just above the 
Run key. If the LED is ON, the Run key is already 
selected as the source, and you may skip this step. Note 
that the default setting depends on the country.
If the Potentiometer Enable LED is OFF, follow the steps below (the table resumes 
action from the end of the previous table).
NOTE: After completing the steps above, the Run Key Enable LED will be ON. This 
does not mean the motor is trying to run; it means that the RUN key is now enabled.
DO NOT press the RUN key at this time—complete the parameter setup first.
Action
Display
Func./Parameter
(Starting point)
“A” Group selected
Press the 
 key.
Speed command source setting
Press the 
 key again.
00 = Keypad potentiometer
01 = Control terminals
02 = Function F001 setting
03 = ModBus network
10 = Calculate function output
Press the 
 key.
00 = potentiometer (selected)
Press the 
  key.
Stores parameter, returns to “A” 
Group list
Action
Display
Func./Parameter
(Starting point)
Speed command source setting
Press the 
 key once.
Run command source setting
Press the 
 key.
01 = control terminals
02 = Run key on keypad
03 = ModBus network input
Press the 
 key.
02 = keypad (selected)
Press the 
  key.
Stores parameter, returns to “A” 
Group list
A – – –
FUNC.
A 0 0 1
FUNC.
0 1
2
0 0
STR
A 0 0 1
1
2
5 0.0
RUN
STOP
RESET
FUNC.
STR
HITACHI
POWER
ALARM
RUN
A
Hz
PRG
Run Key Enable LED
A 0 0 1
1
A 0 0 2
FUNC.
0 1
1
0 2
STR
A 0 0 2