Set the Motor Base Frequency - The motor is designed to operate at a specific AC 
frequency. Most commercial motors are designed for 50/60 Hz operation. First, check 
the motor specifications. Then follow the steps below to verify the setting or correct it 
for your motor. DO NOT set it greater than 50/60 Hz unless the motor manufacturer 
specifically approves operation at the higher frequency.
CAUTION: If you operate a motor at a frequency higher than the inverter standard 
default setting (50Hz/60Hz), be sure to check the motor and machine specifications with 
the respective manufacturer. Only operate the motor at elevated frequencies after getting 
their approval. Otherwise, there is the danger of equipment damage.
Set the AVR Voltage Setting - The inverter has an Automatic Voltage Regulation (AVR) 
function. It adjusts the output voltage to match the motor’s nameplate voltage rating. The 
AVR smooths out fluctuations in the input power source, but note that it does not boost 
the voltage in the event of a brown-out. Use the AVR setting (A082) that most closely 
matches the one for your motor.
• 200V Class: 200 / 215 / 220 / 230 / 240 VAC
• 400V Class: 380 / 400 / 415 / 440 / 460 / 480 VAC
TIP: If you need to scroll through a function or parameter list, press and hold the 
 or 
 key to auto-increment through the list.
To set the motor voltage, follow the steps on the following page.
Action
Display
Func./Parameter
(Starting point)
Run command source setting
Press the 
 key once.
Base frequency setting
 
Press the 
 key.
or
Default value for base frequency. 
US = 60 Hz, Europe = 50 Hz.
Press the 
 or 
 key as needed.
Set to your motor specs (your 
display may be different)
Press the 
  key.
Stores parameter, returns to “A” 
Group list
A 0 0 2
1
A 0 0 3
FUNC.
6 0
5 0
1
2
6 0
STR
A 0 0 3
1
2