Hitachi L200 Manual Do Utilizador

Página de 280
“A” Group: Standard Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–22
Jump Frequencies – Some motors or machines exhibit resonances at particular 
speed(s), which can be destructive for prolonged running at those speeds. The inverter 
has up to three jump frequencies as shown in the graph. The hysteresis around the jump 
frequencies causes the inverter output to skip around the sensitive frequency values.
Jump frequencies
Output
frequency
Frequency command
Hysteresis values
0
A067
A065
A063
A064
A064
A066
A066
A068
A068
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
A063,
A065,
A067
Jump (center) frequency 
setting
Up to 3 output frequencies can 
be defined for the output to 
jump past to avoid motor 
resonances (center frequency)
Range is 0.0 to 400.0 Hz
0.0
0.0
0.0
0.0
0.0
0.0
Hz
JUMP F1 0000.0Hz
JUMP F2 0000.0Hz
JUMP F3 0000.0Hz
A064,
A066,
A068
Jump (hysteresis) 
frequency width setting
Defines the distance from the 
center frequency at which the 
jump around occurs
Range is 0.0 to 10.0 Hz
0.5
0.5
0.5
0.5
0.5
0.5
Hz
JUMP W1 0000.5Hz
JUMP W2 0000.5Hz
JUMP W3 0000.5Hz