Hitachi L200 Manual Do Utilizador

Página de 280
L200 Inverter
Conf
igur
ing
Dr
iv
e P
a
ra
m
e
ters
3–23
PID Control
When enabled, the built-in PID loop calculates an ideal inverter output value to cause a 
loop feedback process variable (PV) to move closer in value to the setpoint (SP). The 
frequency command serves as the SP. The PID loop algorithm will read the analog input 
for the process variable (you specify the current or voltage input) and calculate the 
output.
• A scale factor in A075 lets you multiply the PV by a factor, converting it into 
engineering units for the process.
• Proportional, integral, and derivative gains are all adjustable.
• See 
 for more information.
NOTE: The setting A073 for the integrator is the integrator’s time constant Ti, not the 
gain. The integrator gain Ki = 1/Ti. When you set A073 = 0, the integrator is disabled.
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
A071 PID Enable
Enables PID function,
two option codes:
00... PID Disable
01... PID Enable
00
00
PID Mode     OFF
A072 PID proportional gain
Proportional gain has a range 
of 0.2 to 5.0
1.0
1.0
PID P     0001.0
A073 PID integral time 
constant
Integral time constant has a 
range of 0.0 to 150 seconds
1.0
1.0
sec.
PID I    0001.0s
A074 PID derivative time 
constant
Derivative time constant has a 
range of 0.0 to 100 seconds
0.0
0.0
sec.
PID D    000.00s
A075 PV scale conversion
Process Variable (PV) scale 
factor (multiplier), range of
0.01 to 99.99
1.00
1.00
PID Cnv  001.00%
A076 PV source setting
Selects source of Process 
Variable (PV), option codes:
00... [OI] terminal (current in)
01... [O] terminal (voltage in)
02... ModBus network
03... Calculate function output
00
00
PID INP       OI
A077 Reverse PID action
Two option codes:
00... PID input = SP – PV
01... PID input = –(SP – PV)
00
00
PID MINUS    OFF
A078 PID output limit
Sets the limit of PID output as 
percent of full scale,
range is 0.0 to 100.0%
0.0
0.0
%
PID Vari 0000.0%