Hitachi L200 Manual Do Utilizador

Página de 280
L200 Inverter
Conf
igur
ing
Dr
iv
e P
a
ra
m
e
ters
3–27
Accel/Decel
Standard acceleration and deceleration is 
linear. The inverter CPU can also calculate 
an S-curve acceleration or deceleration 
curve as shown. This profile is useful for 
favoring the load characteristics in particu-
lar applications.
Curve settings for acceleration and decel-
eration are independently selected. To 
enable the S-curve, use function A097 
(acceleration) and A098 (deceleration).
Acceleration period
S-curve
Linear
Accel. curve selection
Target 
freq.
Output
frequency
t
0
A097 = 00
A097 = 01
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
A097 Acceleration curve 
selection
Set the characteristic curve of 
Acc1 and Acc2, two options:
00... linear
01... S-curve
00
00
ACC LINE       L
A098 Deceleration curve 
selection
Set the characteristic curve of 
Acc1 and Acc2, two options:
00... linear
01... S-curve
00
00
DEC LINE       L