BEA 10MATRIX Manual Do Utilizador

Página de 12
75.1046.04   EN  20080505 
 
 
            
 
 
Page 3 of 5
7   Programming
      I.  THE 3 CONFIGURATIONS
 
A.  Configuration A:  Single Loop Detector (MATRIX-S)
 
B.  Configuration B:  Dual Loop Detector in Independent Mode with Dipswitch #10 OFF (MATRIX-D)
 
C.  Configuration C:  Dual Loop Detector in Combined Mode with Dipswitch #10 ON (MATRIX-D)
      II.  POTENTIOMETERS
 
A Potentiometer for Adjustment of the Maximum Duration of a
 
Presence Detection:  from 1 min to Infinity (See PRESENCE TIME)
 
A Potentiometer for Adjustment of the Linear Sensitivity (   f)
 
for the Loop A:  from 0.005% to 0.5% (See SENSITIVITY) 
 
A Potentiometer for Adjustment of the Linear Sensitivity (   f)
 
for the Loop B:  from 0.005% to 0.5% (See SENSITIVITY)
      III.  RELAY CONFIGURATION (DIPSWITCH #3)
A 10 position dip switch is located on the front of the Matrix single detector.  Dip switch 3, 5, 6, 7 and 8 configure the relay, while dip switch 9
controls the duration of the pulse when the Matrix is configured for pulse operation, (as opposed to presence).  Configurations are as follows:
 
DIPSWITCH 3:
OFF= FAIL-SECURE MODE Relay is NOT energized when power is applied.  Relay is energized upon detection only.  In this mode, the NO 
circuit is open, and the NC circuit is closed.  Thus, if a closed circuit is required upon detection, one must use the NO and COM terminals 
since they would close upon detection.  When the Matrix is NOT powered, it is in the same state as it would be for non-detection.
ON = FAIL-SAFE MODE Relay is energized as soon as power is applied and de-energizes upon detection or power loss.  In this mode, upon 
powering the detector, the NO circuit becomes closed, and the NC circuit becomes open.  Thus, if a closed circuit is required upon detection, 
one must use the NC and COM terminals, since they would now be OPEN during non-detection, and would close upon detection.  When the 
Matrix is NOT powered, it is in the same state as it would be for detection.
Configuration A
Single loop
Configuration B
Dual loop in independent mode
Configuration C  
Dual loop in combined mode
Dip Switch 
OFF
ON
OFF
ON
OFF
ON
DS#1
High (loop A) 
Low (loop A) 
 [High –30%] 
High (loop A) 
Low (loop A) 
 [High –30%] 
DS#2
See next table 
High (loop B) 
Low (loop B) 
[High –30%] 
High (loop B) 
Low (loop B) 
[High –30%] 
DS#3
Active mode 
Passive mode 
Active mode 
Passive mode 
Active mode 
Passive mode 
DS#4
ASB OFF 
ASB ON 
ASB OFF 
ASB ON 
ASB OFF 
ASB ON 
DS#5
Relay A : 
Presence on 
loop A 
Relay A : 
Pulse on loop
Relay A : 
Presence on loop A 
Relay A : 
Pulse on loop A 
Not used 
Not used 
DS#6
Relay A : 
Pulse on loop 
A
entry 
Relay A : 
Pulse on loop A 
exit
Relay A : 
Pulse on loop A 
entry 
Relay A : 
Pulse on loop A 
Exit 
Relay B : 
Non-Directional
mode
Relay B: 
Directional AB
mode
DS#7
Relay B : 
Presence on 
loop A 
Relay B : 
Pulse on loop A 
Relay B : 
Presence on loop B 
Relay B : 
Pulse on loop B 
Relay B : 
Pulse on loop B 
Relay B : 
Pulse on loop A 
DS#8
Relay B : 
Pulse on loop 
A
entry 
Relay B : 
Pulse on loop A 
exit
Relay B : 
Pulse on loop B 
entry 
Relay B : 
Pulse on loop B 
exit
Relay B : 
Pulse on loop entry 
Relay B : 
Pulse on loop exit
DS#9
100 ms 
500 ms 
100 ms 
500 ms 
100 ms 
500 ms 
DS#10 
Not used 
Not used 
Independent 
Combined mode 
Independent 
Combined mode 
Δ
Δ
MAX
1 min 10 min
1 hr
2
5
20
Infinity
PRESENCE TIME
hr
hr
hr
MIN
0.5% 0.44%
0.34%
0.25%
0.18%
0.1%
0.005%
SENSITIVITY
MAX
MIN
DETECTION STATUS 
FAIL-SECURE MODE (Active Mode) 
(Relay is not energized upon power-on) 
DIPSWITCH 3 = OFF
FAIL-SAFE MODE (Passive Mode) 
(Relay becomes energized upon power-on) 
DIPSWITCH 3 = ON
NO DETECTION 
The COM and NO terminals are OPEN. 
COM and NC terminals are CLOSED. 
The relay is de-energized. 
The COM and NO terminals are CLOSED. 
COM and NC terminals are OPEN. 
The relay is energized. 
DETECTION
The COM and NO terminals are CLOSED. 
COM and NC terminals are OPEN. 
The relay is energized. 
The COM and NO terminals are OPEN. 
COM and NC terminals are CLOSED. 
The relay is de-energized. 
UPON POWER LOSS 
The COM and NO terminals are OPEN. 
COM and NC terminals are CLOSED 
The relay is de-energized. 
The COM and NO terminals are OPEN. 
COM and NC terminals are CLOSED. 
The relay is de-energized. 
Same
Same