Section 2 — Installation
Remote Aux Connections
The Remote Aux Control Panel consists of three parts:
Remote Aux Panel Assembly
Power supply with power cord
Communications bus cable connector
NOTE:  Due to limited access at the rear of the Remote Aux Panel after it is 
installed in the rack, it is recommended that the communications cable and power 
supply cord be connected and the DIP switches on the rear of the panel be set before 
the panel assembly is installed in the rack.
Cable Installation
 
for connector illustration. This connector must be applied to a shielded 
twisted-pair control cable with a D connector on the opposite end. The D 
connector of the cable will later be plugged into the rear of the switcher 
frame.
CAUTION
Do not plug the D connector in at this time. If power is applied to the switcher, the 
cable line drivers in the switcher may be damaged.
The other end of the cable will be plugged into the Communications Bus 
connector on the rear of the Remote Aux Panel using the supplied 
connector. Any additional panel(s) will be connected to the previous panel. 
Keep in mind that the total length of the cable must not exceed 1000 feet 
(320 M).
Place the D-connector end of the cable so that it will reach J4 (AUX BUS 
CTL) on the Communication I/O Module Slot C10.
Lay the cable from the switcher frame to where the first Remote Aux Panel 
will be. Allow enough cable to reach the control panel connector, and about 
3 feet (1 meter) extra, then cut the cable and strip the wires.