Powerware P93 Manual Do Utilizador

Página de 6
Battery runtimes (in minutes)
iSeries
pSeries
Storage
Cluster
870
890
655
670
690
2105
1350
1600
with
CEC +
CEC +  CEC + 
expansion 
I/O
I/O
I/O
node
nodes
nodes
up to
8 way
32 way
standard enclosure
10 kVA 15 kVA 20 kVA
16 way 16 way 32 way
1 I/O
2 I/O
3 I/O
32 way
1 I/O
3 I/O
7 kW
10.5 kW 14 kW
6.8 kW 4.9 kW 8.3 kW 3.2 kW 6.4 kW
9.6 kW 6.5 kW
3.2 kW 10.5 kW
6.4 kW
13.8 kW
Internal battery
45
26
17
48
79
31
110
50
27
49
110
26
50
17
(1) External 
battery cabinet
90
65
48
98
150
75
240
110
70
108
240
65
110
48
(2) External 
battery cabinets
155
90
75
166
240
130
400
180
96
172
400
90
180
75
Contact Powerware for runtime, application or configuration assistance. 
A DC rated circuit breaker in each battery cabinet allows 
multiple battery strings to be serviced independently of each
other, assuring back up power is always available to the UPS
Removable battery slide-out tray assembles provide “front
access only” and reduce battery maintenance time.
Manufacturer-supplied wiring with quick disconnects provides
plug-and-play capability for line-up and match configurations.
Quick disconnects between battery tray assemblies reduce 
battery maintenance time.
A
Battery cabinets may be daisy-chained together for extended battery runtimes,
(up to 2).
A
Integral configuration, which line up and match, is standard.
1
A
Front-access-only enhances servicing and installation.
A
Slide trays and modular battery packaging makes periodic servicing easy.
A
Cabinets are UL 1778 listed.
A
Flame retardant batteries meet UL 94V2 for computer room installations.
A
Wiring installation.
2
Powerware offers a full line of battery cabinets for the Powerware P93.
Extended Battery Cabinets
1. Battery cabinets can be configured as line up and match or
remotely located. Customer must provide wiring for remotely
located cabinets. 2. If concurrent to P93 Field Installation,
Powerware PN 103003671, IBM PN 97P3604.
Calculating runtime - a guide
Typical runtime is 15 minutes
Formula (runtime in minutes) = [business + (2 x system shutdown) + safety]
Business = _____
Shutdown ____ x 2 = _____
Safety = _____
Total = _____
Powerware
IBM
IBM
Per P93
Part Number
Feature Code
Part Number
Minimum
Maximum
External Battery Cabinet
A13031
6635
97P2663
0
2
Additional options
A
Input/output galvanic isolation
A
Voltage matching transformers
A
Remote status panel 
A
Remote EPO button
Contact
Powerware