Minuteman UPS ED6000T Manual Do Utilizador

Página de 23
 
16
3.5.1.1.4  Configuration # 3: 
Output: One 208VAC 6KVA circuit. Total output load not to exceed 6KVA. 
1.  Connect a jumper wire from L22 to N21. 
2.  Circuit1 (208VAC):    L23 - L1, N22 - L2, G2 - Ground. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
3.5.1.1.5  Configuration # 4: 
Output: One 240VAC 6KVA circuit. Total output load not to exceed 6KVA. 
1.  Connect a jumper wire from L22 to N21. 
2.  Circuit1 (240VAC):    L21 - L1, N22 - L2, G2 - Ground. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
17
3.5.1.1.6  Configuration # 5: 
Output: Two 120VAC circuits (3KVA max load per circuit). and one 208VAC 
6KVA circuit. Total combined output load not to exceed 6KVA. 
1.  Connect a jumper wire from L22 to N21. 
2.  Circuit1 (120VAC):    L22 - Line, N22 - Neutral, G2 - Ground. 
3.  Circuit2 (120VAC):    L21 - Line, N21 - Neutral, G2 - Ground. 
4.  Circuit3 (208VAC):    L23 – L1, N22 – L2, G2 - Ground. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
3.5.1.1.7 Configuration 
#6: 
Output: Two 120VAC circuits (3KVA max load per circuit) and one 240VAC 
6KVA circuit. Total combined output load not to exceed 6KVA. 
1.  Connect a jumper wire from L22 to N21. 
2.  Circuit1 (120VAC):    L22 - Line, N22 - Neutral, G2 - Ground. 
3.  Circuit2 (120VAC):    L21 - Line, N21 - Neutral, G2 - Ground. 
4.  Circuit3 (240VAC):    L21 – L1, N22 – L2, G2 - Ground.