16
3.5.1.1.4 Configuration # 3:
Output: One 208VAC 6KVA circuit. Total output load not to exceed 6KVA.
1. Connect a jumper wire from L22 to N21.
2. Circuit1 (208VAC): L23 - L1, N22 - L2, G2 - Ground.
2. Circuit1 (208VAC): L23 - L1, N22 - L2, G2 - Ground.
3.5.1.1.5 Configuration # 4:
Output: One 240VAC 6KVA circuit. Total output load not to exceed 6KVA.
1. Connect a jumper wire from L22 to N21.
2. Circuit1 (240VAC): L21 - L1, N22 - L2, G2 - Ground.
2. Circuit1 (240VAC): L21 - L1, N22 - L2, G2 - Ground.
17
3.5.1.1.6 Configuration # 5:
Output: Two 120VAC circuits (3KVA max load per circuit). and one 208VAC
6KVA circuit. Total combined output load not to exceed 6KVA.
6KVA circuit. Total combined output load not to exceed 6KVA.
1. Connect a jumper wire from L22 to N21.
2. Circuit1 (120VAC): L22 - Line, N22 - Neutral, G2 - Ground.
3. Circuit2 (120VAC): L21 - Line, N21 - Neutral, G2 - Ground.
4. Circuit3 (208VAC): L23 – L1, N22 – L2, G2 - Ground.
2. Circuit1 (120VAC): L22 - Line, N22 - Neutral, G2 - Ground.
3. Circuit2 (120VAC): L21 - Line, N21 - Neutral, G2 - Ground.
4. Circuit3 (208VAC): L23 – L1, N22 – L2, G2 - Ground.
3.5.1.1.7 Configuration
#6:
Output: Two 120VAC circuits (3KVA max load per circuit) and one 240VAC
6KVA circuit. Total combined output load not to exceed 6KVA.
6KVA circuit. Total combined output load not to exceed 6KVA.
1. Connect a jumper wire from L22 to N21.
2. Circuit1 (120VAC): L22 - Line, N22 - Neutral, G2 - Ground.
3. Circuit2 (120VAC): L21 - Line, N21 - Neutral, G2 - Ground.
4. Circuit3 (240VAC): L21 – L1, N22 – L2, G2 - Ground.
2. Circuit1 (120VAC): L22 - Line, N22 - Neutral, G2 - Ground.
3. Circuit2 (120VAC): L21 - Line, N21 - Neutral, G2 - Ground.
4. Circuit3 (240VAC): L21 – L1, N22 – L2, G2 - Ground.