3.6.1.6  The UPS will perform another self-test and the LCD display will change 
from drawing C to drawing D. During the self-test the UPS will switch to 
the Battery mode for approximately 4-seconds, then the LCD display will 
change from drawing D to drawing E1. Once the UPS successfully passes 
the self-test the LCD will display drawing F. If the UPS fails the self-test the 
LCD will display drawing E2 then the LCD will display an error code or 
error status.  See Section 2.2 for Error codes and Section 4 for 
Troubleshooting. 
 
 
 
 
D  
 
 
 
                             
  * It shows “test” during the self-test. 
 
 
 
E1 
 
 
 
 
                               
* It shows “OK” if the self-test was successful. 
 
 
 
 
E2  
 
 
 
           
* It shows “Fail” if the UPS fails the self-test. 
 
 
 
 
 
 
 
                                 
* It shows “208VAC” Utility Input. 
 
 
21
3.6.1.7  The UPS has successfully passed the start-up procedure. The UPS will 
charge the batteries whenever the UPS is connected to an AC source and 
there is an acceptable AC voltage present. It is recommended that the 
UPS's batteries be charged for a minimum of 8-hours before use. However 
the UPS may be used immediately, but the “On-Battery” runtime maybe 
less than normally expected.  NOTE:  If the UPS is going to be out of 
service or stored for a prolonged period of time, the batteries must be 
recharged for at least 12-hours every 3 months. 
 
3.6.2  Startup in Battery Mode (Cold Start) 
 
3.6.2.1  Switch the UPS’s input circuit breaker (on the rear panel) to the On 
position. 
3.6.2.2  Press and hold the UPS On Switch (on the front panel) 
 for 
approximately 3-seconds, then release, the audible alarm will sound 2-
beeps. The LCD display will scroll from drawing A to drawing G this will 
take approximately 10-seconds. 
3.6.2.3  During this 10-seconds press and hold the UPS On Switch again 
 for 
approximately 3-seconds, then release, the audible alarm will sound 2-
beeps. The LCD display will change from drawing G to drawing H, the 
UPS will be in self-test mode. The UPS will provide an output within 
approximately 1-minute, and then the LCD display will display drawing I. If 
the UPS On switch was not pressed within the 10-seconds, the UPS will 
automatically turn off. You will have to repeat the above steps again. 
 
 
 
 
 
 
 
                 
* It shows “Off”, which means the UPS pre-start is successful.   
 
 
 
 
 
 
 
                 
* It shows the Utility input is “0VAC”.