Operating Manual LP 33 Series 30 & 40 kVA 
Code 
Alarm 
Meaning 
 
4118 
BATTERY 
FAULT 
During battery test the DC voltage falls under the critical 
level. 
If the boost voltage has not been reached within 24 hours, 
then the charge voltage returns to floating voltage. 
Battery test is stopped. 
4130 
TURN ON RECT. 
OR SHUTDOWN UPS 
Rectifier and inverter are OFF. 
The DC power supply is discharging the battery slowly. 
Rectifier must be restarted or battery must be disconnected 
in order to avoid damages. 
4140 
RECTIFIER 
CONTROL FAILURE 
Rectifier voltage hasn’t reached the set value. 
Probably fault on regulation loop. 
The DC capacitors are not equally charged (more of 50 VDC 
of difference). 
The rectifier is switched OFF. 
4301 
INVERTER 
FUSES FAILURE 
Inverter output fuses blown. 
Signaled by electronic detector. 
Inverter can be started manually after replacement of fuses. 
4304 
K7 CLOSING 
FAILURE 
K7 not closed despite a closing command being done. 
Signaled by auxiliary contact. 
Load will be supplied by mains. 
4305 
K7 OPENING 
FAILURE 
K7 not open despite an opening command being done. 
Signaled by auxiliary contact. 
Load will be supplied by mains. 
4312 
INV. VOLTAGE 
OUT OF TOLERANCE 
Inverter output voltage is out of the tolerances defined in 
respective parameter (±10%). 
Inverter is switched OFF. 
4320 
ISMAX 
DETECTION 
Detection of inverter bridge (Is) current limitation cause 
inverter OFF and automatic restart (message 320). 
After 3 times inverter switches OFF for persistent Is max 
detection in time. 
Inverter switch OFF, and it can be restarted manually. 
4340 
INVERTER 
CONTROL FAILURE 
The slave oscillator is not synchronized with the master, thus 
causing the shutdown of it’s inverter. 
4347 
OSCILLATOR 
FAILURE 
Auto calibration of the Inverters free-run frequency was not 
possible. 
The oscillator frequency of this unit is out of tolerance. 
4402 
RECTIFIER 
CANNOT BE TURNED ON 
The rectifier cannot be turned on because the DC link 
voltage has not reached the requested value. 
4404 
K6 CLOSING 
FAILURE 
K6 not closed despite a closing command being done. 
Signaled by auxiliary contact. 
The load cannot be supplied by electronic bypass. 
4405 
K6 OPENING 
FAILURE 
K6 not open despite an opening command being done. 
Signaled by auxiliary contact. 
4410 
BYPASS MAINS 
OUT OF TOLERANCE 
The mains bypass voltage is out of the tolerances (±10%). 
K6 opens, synchronization with mains is inhibited and 
transfer to mains is blocked.