GE LP 33 Manual Do Utilizador

Página de 57
Modifications reserved 
Page 25/57 
OPM_LPS_3UO_30K_40K_0US_V010.doc 
Operating Manual LP 33 Series 30 & 40 kVA 
Code 
Alarm 
Meaning 
 
4520 
NO INVERTER 
POWER 
The load supplied by utility is over 100%. 
The load remains blocked on utility as long as alarm 
overload is active. 
4530 
LOAD LOCKED 
ON MAINS 
Load is locked on mains because 3 transfers on mains have 
been detected in a short time (default 30 seconds). 
Transfer will be free again after a time defined by respective 
parameter (default 30 seconds). 
4531 
LOAD ON MAINS 
BY ERROR DETECTOR 
Load is transferred to mains because the error detector 
detected a disturbance on the output voltage. 
4563 
EMERGENCY OFF 
ACTIVATED 
Alarm after detection of an Emergency Off from an external 
safety device connected on Customer Interface. 
Consequently K4, K6 and K7 open and shut down inverter, 
booster and rectifier. 
4570 
OVERLOAD 
The UPS-System is in an overload condition >125% on 
inverter, or >150% on mains. 
A sequence of “stop operation” starts. 
Time out depending on load quantity. 
4571 
OVERLOAD: 
LOAD ON MAINS 
With mains bypass supply available and load >115%, the 
load is transferred on mains. 
Load will be transferred again automatically on inverter 
when load will be <100%. 
4581 
INVERTER AND 
MAINS NOT SYNCH. 
The voltages of mains and inverter are not synchronized, 
which causes the opening of K6. 
4697 
BATTERY 
OVERTEMPERATURE 
The battery temperature exceeds the value inserted in 
parameter. 
Disabled with parameter (service only).
 
4698 
BATTERY POWER 
INSUFFICIENT 
In case of utility failure, with the actual load, the autonomy 
time would result below “stop operation” time (default 3 
minutes). 
4700 
DC LOW 
Battery voltage is at the lowest limit. 
Shutdown of inverter until the battery voltage reaches the 
value in respective parameter. 
4900 
LOAD LOCKED 
ON INVERTER 
The load is locked on Inverter following 3 load transfers 
within 30 seconds. 
After time out of the value in respective parameter (default 
30 seconds), bypass will be free. 
4955 
OVERTEMPERATURE 
An overtemperature condition has been detected on 
inverter. 
Elapsed “stop operation” time, inverter shutdown. 
With mains available, load is transferred on mains. 
4998 
LOAD OFF DUE TO 
EXTENDED OVERLOAD 
Load Off after time-out of “stop operation” for overload on 
inverter or bypass (time depending on the % of overload). 
4999 
LOAD OFF DUE TO 
UBATT OR TEMP. 
Load Off after time-out of “stop operation” with missing 
mains due to battery low voltage or overtemperature 
condition.